should there be continuity between neutral and ground

by Camren Kerluke V Published 3 years ago Updated 2 years ago
image

Once the outlet is connected to the wires in the wall (or plugged in in the OP's case) there will be continuity between ground and neutral because they are connected in your main breaker panel, but if the GFCI (or any other outlet) is just sitting on a table, they should not have continuity.Jul 11, 2019

Full Answer

Should there be resistance between neutral and ground?

Should There Be Resistance Between Neutral And Ground? All neutral wires of the same earthed (grounded) electrical system should have the same electrical potential, because they are all connected through the system ground. Neutral conductors are usually insulated for the same voltage as the line conductors, with interesting exceptions.

Do all neutral wires have the same electrical potential?

All neutral wires of the same earthed (grounded) electrical system should have the same electrical potential, because they are all connected through the system ground. Neutral conductors are usually insulated for the same voltage as the line conductors, with interesting exceptions. How do you test earth continuity?

Which phase wires have continuity between them?

All phase wires, the neutral wire and the ground wire inside of the 120/208 panel have continuity between them all. I checked for continuity between the phase wires coming off of the breaker in the 480 volt panel that feeds the transformer and they have continuity between them as well.

What about continuity between neutral and secondary leads in 120/208 panel?

What about the continuity between the neutral and the 3 secondary leads inside of the 120/208 panel? Click to expand... With no main breaker in that panel, which is most likely a code violation, you have no isolation and if everything is in working condition you will have continuity between all four secondary leads.

How many Q&A communities are there on Stack Exchange?

What size box do I use for a GFCI?

Can you run a Romex through a wall?

How does a test button work?

What is the meaning of "back up"?

Is GFCI a codevio?

Why do plugs go on cordage?

See 4 more

About this website

image

Should there be continuity between neutral and ground in a sub panel?

The feed for your sub panel comes from your main panel the grounded conductor neutral and grounding conductor equipment ground are connected in the main panel so measuring continuity in a sub is normal even when the grounded conductor is isolated from the box and the grounding conductor.

Does earth and neutral show continuity?

Can continuity be checked between Earth and neutral? Yes, you can check but it will show discontinuity, because Earth and Neutral nodes might not have same potential. If both the points are connected by a conductor then its obviously will show continuity.

Should a ground have continuity?

There should be NO continuity (total resistance), as these two should be seperate circuits. If there is continuity, there is a short in the system in which the ground and hot lines are connected.

Should there be resistance between neutral and ground?

Q “What is the resistance between neutral and ground or earth?” Ideally zero ohms, although as that's not achievable, a fraction of an ohm will do. Note, that's for TN-S and TN-C-S supply systems. Realistically, a TT system could be a few tens of ohms depending on ground conditions.

How do you check continuity on a neutral wire?

0:231:15How to Identify Hot, Neutral and Ground Wires using ... - YouTubeYouTubeStart of suggested clipEnd of suggested clipAnd finally touch the red probe to each exposed wire. If you don't get a voltage reading the wire isMoreAnd finally touch the red probe to each exposed wire. If you don't get a voltage reading the wire is neutral. If you get a reading the wire is hot you can also use color coding to identify.

Why do I have voltage between neutral and ground?

Neutral-to-earth voltage can be caused by a number of factors, both in and around the farm. The amounts of minerals and moisture in the soil, subsoil and rock strata, and the varying water table level can affect any grounding system and change N-E voltages.

How do you test ground continuity?

How to Test for Continuity with a Digital MultimeterFirst insert the black test lead into the COM jack.Then insert the red lead into the VΩ jack. ... With the circuit de-energized, connect the test leads across the component being tested. ... The digital multimeter (DMM) beeps if a complete path (continuity) is detected.More items...

Should there be continuity between positive and ground?

For those interested, the answer to my original question is NO – there should not be any continuity between the positive and negative battery terminals when the battery is unplugged (as this would indicate a short circuit!).

What is grounding continuity?

The purpose of a ground continuity test is to verify that all conductive parts of a product that are exposed to user contact are connected to the power line ground (the “green” wire).

What is the standard resistance value between the neutral and earth?

Ideally a ground should be of zero ohms resistance. There is not one standard ground resistance threshold that is recognized by all agencies. However, the NFPA and IEEE have recommended a ground resistance value of 5.0 ohms or less.

Does a neutral wire carry current?

Neutral wire carries the circuit back to the original power source. More specifically, neutral wire brings the circuit to a ground or busbar usually connected at the electrical panel. This gives currents circulation through your electrical system, which allows electricity to be fully utilized.

What is the insulation resistance between neutral and earth?

Thus, the resistance between poles or to earth must never be less than half of one meg ohm (0.5 M Ohms) for the usual supply voltages.

Should there be continuity between positive and ground?

For those interested, the answer to my original question is NO – there should not be any continuity between the positive and negative battery terminals when the battery is unplugged (as this would indicate a short circuit!).

Should there be continuity between phases?

Each phase to phase must have a continuity if winding is OK. If any particular phase fails the continuity test, your motor is probably burnt.

Should transformers have ground continuity?

Resolution: Continuity is normal between the phases of the primary and secondary sides of the transformer even if they're not energized (H1 and H2 or H2 and H4 etc) or (X1 and X2 or X2 and X3 etc).

What is the difference between neutral and earth?

The most significant difference between them is that the neutral wire is used as a return path for electric current in an AC system, while the earth wire is used as a safety wire in any electric system. However, both the earth wire and the neutral wire have the same voltage equal to zero.

Continuity between all phases, neutral and ground

In the 120/208 panel you are reading through either connected loads or through the transformer secondary windings the only open continuity test you would be able to perform is the load side of main breaker with the breaker open and with no loads connected.

Continuity between ground and neutral at subpanel

So let me preface this by saying that I am a journeyman electrician but I do lack a bit in the theory side of electricity. My question is should there be continuity between ground and neutral in a subpanel.

Neutral to Ground shows continuity | DIY Home Improvement Forum

THe grounding SYSTEM is comprised of the GEC and EGC, panel ground bar, and at the panel the neutral/grounded conductor are all common at the panel and had better have the same ground potential through the residence, except under fault conditions. That a system can operate without a GEC has nothing to do with this discussion and was NOT MENTIONED, by me, the OP or the person that responded to ...

Nuetral and ground continuity. | Mike Holt's Forum

In this and other expense cases, the neutral wire is carrying current, but is at voltage very close to ground. Because of the bond at the main panel, if the neutral touches a grounded metal object some current will flow back to the secondary of the service transformer through the ground path rather than the neutralBut the voltage difference will be so low that the will not be a dangerous spark.

Continuity between line and ground after switching main ... - reddit

Any type of plugged in resistive element or incandescent light bulb will show continuity through the circuit. The filament in a light bulb or the heating element in a plugged in toaster/hot plate/etc is continuous from hot to neutral and your neutral is attached to the ground at your service panel.

GFCI – should my neutral and ground have continuity?

Once the outlet is connected to the wires in the wall (or plugged in in the OP’s case) there will be continuity between ground and neutral because they are connected in your main breaker panel, but if the GFCI (or any other outlet) is just sitting on a table, they should not have continuity.

What is a grounding system?

THe grounding SYSTEM is comprised of the GEC and EGC, panel ground bar, and at the panel the neutral/grounded conductor are all common at the panel and had better have the same ground potential through the residence, except under fault conditions.

What would happen if there was no water bond?

If there was no water bond or ground rods connected to the service, nothing would change and the ground at a receptacle would still be useful since the service neutral is what actually provides the fault path.

Where are grounding and grounding conductors connected?

The grounded conductor and the grounding conductor are connected to the same place in service entrance panel which are in turn connected to the grounded conductor from the meter.

How many conductors does an arcing socket have?

I just replaced an arcing socket. Surprisingly, it has 3 conductor wire coming into the box. I found that this receptacle is on its own breaker, going to the new, grounded panel.

What is the purpose of ground at a receptacle?

The purpose of the ground at the receptacle is to provide a fault path. If there was no water bond or ground rods connected to the service, nothing would change and the ground at a receptacle would still be useful since the service neutral is what actually provides the fault path.

What should the ground be at the same potential?

The ground at the panel should be at the same potential (assuming no shorts to ground) as all the other grounds in a residence.

What happens if you unbond a ground and neutral?

Now, if you unbond the ground and neutral, there is a very high probability that the resistance of that ground will not be great enough to trip a breaker.

Can you use non metalic pipe in Chicago?

We cant use non metalic pipe in chicago. All internal pipe has to be metal. The only time we use pvc is when we are putting it under ground, and even then I prefer to use rigid conduit.

Is conduit under ground nuts?

Metal conduit under ground is even more nuts than EMT in wood framed homes.

Can you test grounding conductors?

Yup, sure is. As you have essentially stated, the grounded and grounding conductors are connected at the service disconnect. In fact, you want the lowest resistance reading you can get between them. For a more comprehensive test, you could remove one or the other at the source and should read many millions of ohms.

How many Q&A communities are there on Stack Exchange?

Stack Exchange network consists of 178 Q&A communities including Stack Overflow, the largest, most trusted online community for developers to learn, share their knowledge, and build their careers.

What size box do I use for a GFCI?

Alternate: if you want to put a GFCI and feed another plain outlet for 4 sockets then use a 4-11/16" box and mud ring, otherwise it won't all fit. You can use a plain receptacle and normal/Decora split cover plate.

Can you run a Romex through a wall?

If it's going to be mounted onto a wall anyway, you should either run that Romex through the walls, or run it (or better, individual THHN wires) through some sort of surface mounted conduit, e.g. Legrand Wiremold, plain EMT, whatever. You can feed off a flush-mount box with a Wiremold starter box, or a plain EMT extension box.

How does a test button work?

Is the TEST button pushed in? The way the test works is by internally connecting (through a resistor) things that should not be connected to make sure it trips. If it's pushed in, you'll get false readings.

What is the meaning of "back up"?

Making statements based on opinion; back them up with references or personal experience.

Is GFCI a codevio?

Putting a GFCI in a box on a cable is a codevio. Using Romex for cordage is a codevio. And using junction boxes for portable boxes is also a code vio, but let's at least use a tough box and a strain relief, eh? Here's what you need.

Why do plugs go on cordage?

Because plugs are not designed/allowe/listed for solid wire. Plugs should only go on cordage, which are stranded wire by definition.

image

1.GFCI - should my neutral and ground have continuity?

Url:https://diy.stackexchange.com/questions/168954/gfci-should-my-neutral-and-ground-have-continuity

24 hours ago There is no continuity between Neutral and Ground. Neutrality is a state of being, not a location.

2.Neutral to Ground shows continuity - DIY Home …

Url:https://www.diychatroom.com/threads/neutral-to-ground-shows-continuity.194375/

13 hours ago  · Once the outlet is connected to the wires in the wall (or plugged in in the OP's case) there will be continuity between ground and neutral because they are connected in your main …

3.Nuetral and ground continuity. | Mike Holt's Forum

Url:https://forums.mikeholt.com/threads/nuetral-and-ground-continuity.105532/

36 hours ago Once the outlet is connected to the wires in the wall (or plugged in in the OP's case) there will be continuity between ground and neutral because they are connected in your main breaker …

A B C D E F G H I J K L M N O P Q R S T U V W X Y Z 1 2 3 4 5 6 7 8 9