by Everardo Lubowitz Published 2 years ago Updated 2 years ago

“The maximum setting of the ground-fault protection system shall be 1200 amperes, and the maximum time-delay shall be one second for ground-fault currents equal to or greater than 3000 amperes.

Although the ground fault currents can reach values up to thousands of amps , the NEC 2011 in the article 230.95(A) mentions that the maximum setting for ground fault protection must be 1200Amps and the maximum time-delay must be 1 second for currents of 3000Amps or higher.

Full Answer

What is the zone of protection of a a-ground relay?

A ground relay must detect all phase-to-ground faults within its defined zone of protection under conditions which produce minimum fault current. The ground relay zone of protection can be defined as a current threshold or measured impedance.

How many levels of ground fault protection do I Need?

It is required that two levels of ground fault protection should be supplied, with protection both on the main circuit breaker, as well as the feeder circuit breaker. The devices must be coordinated to ensure that the feeder circuit breaker will trip prior to causing the main circuit breaker to trip.

When does the switch control start the ground fault duration time thresholdtimer?

If an overcurrent condition is present at the expi- ration of the Time Blocktimer, the switch control starts the Ground Fault Duration Time Thresholdtimer. Note:When the Ground Current Inrush Restraint Multipliersetpoint is

How does a phase-to-ground fault work?

When a phase-to-ground fault occurs, the return path of the ground fault current is from the ground bus to the neutral bus through the ground strap. The ground strap current sensor senses this current and applies it directly to the ground trip element.

What is ground fault protection?

What is a ground fault circuit interrupter?

What voltage is required for a service disconnect?

What is GFCI protection?

What causes electrical explosions?

Is GFCI protection mandatory?

See 3 more

About this website

What is the maximum time delay setting for the ground fault equipment?

The maximum setting of the ground-fault protection shall be 1200 amperes, and the maximum time delay shall be one second for ground-fault currents equal to or greater than 3000 amperes.

What is the maximum setting of ground fault protection?

“The maximum setting of the ground-fault protection system shall be 1200 amperes, and the maximum time-delay shall be one second for ground-fault currents equal to or greater than 3000 amperes.

What is the maximum allowable time delay result for a ground fault relay?

The maximum time delay is one second for ground-fault currents equal to or greater than 3,000 amperes. These equipment protection requirements are a result of a history of destructive burndowns of electrical equipment operating at these voltage levels.

What is the maximum time delay permitted for the GFI to operate where the ground fault current is 4000 amperes?

The setting of the GFPE must not be greater than 1,200A and the maximum time delay before operation shall not exceed one second (60 cycles) for ground-fault currents of 3,000A or greater.

In which article of the NEC can the maximum permitted overcurrent protection requirements for transformers be found?

Section 450.3NEC® Section 450.3 contains the requirements for overcurrent protection of transformers.

What is ground fault current?

A ground fault occurs when electricity takes an unplanned path to ground. The current drastically increases and causes the breaker to trip. A ground fault can be caused by damaged appliances, incorrect wiring, or worn wire insulation.

What is the maximum size time delay fuse that can be used for an ac motor?

What is the maximum allowable rated time-delay fuse, with exception, that can be used with a 20 HP, 460 VAC, 3 – phase motor if the maximum rating is insufficient for motor start-up? The maximum allowable rating for this device is 60A. The calculated 61A shall not be exceeded, so it must be sized down to 60A.

What level of ground fault current is considered in electronic detection for people protection?

Ground fault interrupters designed to provide life protection must open a circuit at 5 milliamps (± 1 milliamp). Ground fault protection for equipment must open a circuit when ground fault current reaches 30 milliamps.

What is the approximate current at which a ground fault detector will open the circuit?

++ GFCI protectors open the circuit when approximately 5 milliamperes of ground-fault current are sensed.

Where is ground fault protection required?

Where GFCIs Are Required. GFCI protection is required for 125-volt to 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to the ground. GFCI receptacles are required in bathrooms, garages, crawl spaces, basements, laundry rooms and areas where a water source is present.

What is ground fault protected?

Ground fault protection is equipment protection from the effects of ground faults. The National Electrical Code® (NEC® ) has specific ground fault equipment protection requirements in 215.10, 230.95, 240.13 and 517.17. Ground fault relays (or sensors) are used to sense low magnitude ground faults.

Which of the following requires ground fault protection of equipment to be performance tested when first installed on site?

The ground fault protection system shall be performance tested when first installed in accordance with NEC Article 230.95. The test shall be conducted in accordance with instructions that shall be provided with the equipment.

What is ground fault protected?

Ground fault protection is equipment protection from the effects of ground faults. The National Electrical Code® (NEC® ) has specific ground fault equipment protection requirements in 215.10, 230.95, 240.13 and 517.17. Ground fault relays (or sensors) are used to sense low magnitude ground faults.

Where is ground fault protection required?

Where GFCIs Are Required. GFCI protection is required for 125-volt to 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to the ground. GFCI receptacles are required in bathrooms, garages, crawl spaces, basements, laundry rooms and areas where a water source is present.

What is GFCI protection?

The GFCI is designed to protect people from severe or fatal electric shocks but because a GFCI detects ground faults, it can also prevent some electrical fires and reduce the severity of other fires by interrupting the flow of electric current.

What is the earth fault protection?

Earth fault protection is intended to protect equipment when an insulation fault occurs, for instance a direct contact between a life conductor and earth.

The Differences between GFCI, IDCI, and GFPE

The most important thing to understand about ground fault protection devices is that one type is to protect personnel and the other is to protect electrical equipment, the latter having different trip levels for different types of protection. Three basic ground fault systems or leakage current protection devices are used in the electrical system: ground fault protection for personnel that are ...

Ground Fault Equipment Protection (30mA) Square D Miniature Circuit ...

When it comes to Ground Fault Equipment Protection (30mA) Square D Miniature Circuit Breakers for Panelboards and Load Centers, you can count on Grainger. Supplies and solutions for every industry, plus easy ordering, fast delivery and 24/7 customer support.

Leaflet Ground Fault Equipment Protector (GFEP) Information tool - ABB

1SXU430091L0201, May 2013 ABB Inc. Low Voltage Products 16250 W. Glendale Drive New Berlin, WI 53151 Technical Support & Customer Service Phone: 888-385-1221, Option 4

Ground fault protection - GFCI or GFPE - there is a difference

A ground-fault circuit-interrupter (GFCI) is an electrical device, either a receptacle or circuit breaker, which is designed to protect people from electric shock. GFCI protection should not be confused with ground-fault protection for equipment or grounding in general. Even if a system is properly grounded, minor faults in a circuit can cause a dangerous shock to a person using an appliance ...

Understanding Ground Fault and Leakage Current Protection

01 Understanding Ground Fault and Leakage Current Protection GFCIs The definition of a ground-fault circuit interrupter is located in Article 100 of the

What is the maximum time delay setting for the ground-fault equipment?

The maximum setting of the ground-fault protection shall be 1200 amperes, and the maximum time delay shall be one second for ground-fault currents equal to or greater than 3000 amperes. The code continues to describe specifics regarding the testing of this equipment.

What is the maximum current setting of the ground-fault protection for an electrical equipment where the trip coordination is not required?

All delta connected services are not required to have ground fault protection. The maximum setting for the ground fault relay (or sensor) can be set to pick up ground faults at a maximum of 1200A and actuate the main switch or circuit breaker to disconnect all phase conductors.

What level of ground-fault current is considered in electronic detection for equipment protection?

Ground fault interrupters designed to provide life protection must open a circuit at 5 milliamps (± 1 milliamp). Ground fault protection for equipment must open a circuit when ground fault current reaches 30 milliamps.

What is a ground-fault setting?

A ground fault is an inadvertent contact between an energized conductor and ground or equipment frame. The return path of the fault current is through the grounding system and any personnel or equipment that becomes part of that system. Ground faults are frequently the result of insulation breakdown.

What is the maximum ground-fault protection setting permitted by the CEC?

Since the maximum setting permitted by Section 230.95 is 1 second (60 cycles), the time setting for this example should not be in excess of a quarter of a second. The maximum ampere setting is normally figured at about 10 percent of the size of the main disconnecting means.

What causes generator over current?

An overcurrent event on a synchronous generator set occurs any time the load demands more current than the nameplate rating of the generator set. The overcurrent can be caused by the starting of a large motor, the inrush associated with the charging of a transformer, a short circuit or any other number of events.

What is ground-fault overvoltage?

Ground fault overvoltage can occur in situations in which a four-wire distribution circuit is energized by an ungrounded voltage source during a single-phase-to-ground fault. … It identifies the relevant physical mechanisms, quantifies expected levels of overvoltage, and makes recommendations for optimal mitigation.

How many cycles does GFP 2 respond to?

GFP-2 responds after a delay of 6 cycles to any fault that hasn’t been cleared by GFP-3. GFP-3 responds instantaneously to any fault on the branch circuit it protects. In this scheme, the time delays necessary for conventional time-current coordination may compromise equipment protection.

What is GFP-1?

GFP-1 responds instantaneously to ground faults on the line side of GFP-2. GFP-2 responds instantaneously to faults on the load side of its location to the line side of GFP-3 and sends a restraining signal to GFP-1. GFP-3 responds instantaneously to faults on its load side and sends a restraining signal to GFP-2.

Is 120/240 a single phase?

120/240 is single phase, not 2 phase. Just because there are 2 hot conductors does not mean it is called 2 phase. It is fed by one transformer with one phase conductor and one neutral, and the secondary side is center tapped to create a grounded conductor which is the neutral.

What is a ground fault circuit interrupter?

The definition of a ground-fault circuit interrupter is located in Article 100 of the NEC and is as follows: “A device intended for the protection of personnel that functions to de-energize a circuit or portion thereof within an established period of time when a current to ground exceeds the values established for a Class A device. ”.

What is GFPE in electrical?

GFPE (Ground-Fault Protection of Equipment) — Intended for the protection of equipment by disconnecting all ungrounded conductors of a circuit at current levels less than that of a supply circuit overcur- rent protective device. This type of device is designed typically to trip in the 30 mA or higher range, and therefore is not used for personnel protection. This type of device may be provided as required by NEC Sections 210.13, 240.13, 230.95, and 555.3. UL guide information for Ground-Fault Sensing and Relay Equipment can be found under the UL Product Category KDAX.

What is an EGFPD?

EGFPD (Equipment Ground-Fault Protective Device) — Intended for applications such as fixed electric deicing and snow melting equipment, as well as fixed electric heating equipment for pipelines and vessels, in accordance with Articles 426 and 427 in the NEC. This device operates to disconnect the electric circuit from the source of supply when the ground-fault current exceeds the ground- fault pick-up level marked on the device, typically 6 mA to 50 mA. UL guide information for Ground-Fault Protective Devices can be found under the UL Product Category FTTE.

Why is UL used?

To help mitigate electrical shock hazards, UL has been at the forefront of detector research, technology and standards development. Statistics have shown that devices described in this article have proven to be an effective means to improve safety in residential occupancies and other electrical installations.

How long have GFCIs been in use?

July 23, 2019. by. Ground-fault circuit interrupters (GFCIs) have been in use for over 40 years, and have proven themselves to be invaluable in the protection of personnel from the hazard of electric shock.

What is ground fault relay?

Ground fault relays are not simple and the ultimate reliability depends on thereliability of each element such as solid state sensor, monitor, control wiring,control power source, shunt trip, and circuit disconnecting means. If one element is incorrectly wired, inoperative, miscalibrated, or damaged, the lowlevel ground fault protection may be negated. If the system neutral is incorrectlyor accidentally grounded on the load side of the sensor, a ground fault canhave a return path over the neutral and never trip the relay. Unfortunately, anuisance outage often encourages the building owner or maintenance crew todisconnect the ground fault relay so that the power “stays on.”Ground fault relays are not maintenance free devices. Ground fault relayequipment relies on sensing equipment, shunt trips, switching devices, controlcircuits, etc. Complete periodic maintenance and electrical testing of theequipment by qualified personnel is necessary since it has components andmechanisms that can fail, malfunction, and/or lose calibration.

What is 230.95 equipment fault protection?

Equipment ground fault protection of the type required in 230.95 is nowrequired for each disconnect rated 1000A or more, 480Y/277V systems, thatwill serve as a main disconnect for a separate building or structure. Refer to215.10and 230.95.

What is the effect of a fuse protecting the circuit?

The effect of a fuse protecting the circuit is to limit the instantaneous peak current and thermal or heating effect current to a value less than that whichwould flow in the first half cycle had the fuse not been in the circuit. Current-limitation for high level ground faults can substantially reduce the damagingeffect.

How does zero-sequence mutual coupling affect ground overcurrent?

Zero-sequence mutual coupling also affects the performance of ground overcurrent elements that use zero-sequence current as an operating quantity. The mutual coupling affect can reduce the sensitivity of zero-sequence overcurrent elements in detecting faults at the remote end of the line.

Why can't a quadrilateral distance element detect fault resistance?

quadrilateral distance element cannot detect the fault resistance specified by the resistive element reach setting due to current infeed into the fault resistance from the other line terminal.

What causes zero and negative overcurrent?

System unbalances caused by line configuration, in-line load switching, or unbalanced loads can affect the sensitivity of zero- and negative-sequence overcurrent elements. Ground distance elements are relatively immune to system unbalances primarily because they cannot be set as sensitive as overcurrent elements.

What is the advantage of a distance relay?

The major advantage of distance relays is that the zone of operation is a function of the protected line impedance, which is a constant, and is relatively independent of the current and voltage magnitudes. The distance relay has a fixed reach, as opposed to overcurrent relays for which the zone of protection varies with respect to changes in the source impedance.

What is the quadrilateral ground distance?

Each side of the quadrilateral characteristic shown in Figure 4 represents a different element: the reactance element (top line), positive and negative resistance boundaries (right and left sides, respectively), and the directional element (bottom line). The characteristic shown in Figure 4 represents the typical quadrilateral characteristic for a radial system.

Why are MHO ground distance elements easier to set than quadrilateral ground distance elements?

This is because there are fewer settings required and less influence on the mho element by unequal source and line impedance angles.

Why use time delay?

Using a time delay to coordinate with the switch opening can work well since the opening of the switch is equivalent to a transient condition ( i.e., the unbalance is only momentary). Using a time-step function provides good coordination with the opening of the switch as well as high-resistance fault coverage.

How to determine the correct setting for a ground fault?

To determine the proper setting, look at the source-side device’s ground TCC curves for a range of fault duty, up to the maximum available ground fault current at the sectionalizing switch. The switch control must be able to detect the fault prior to the source-side device tripping. See Figure 2 on page 9 for an example. Follow these steps to configure the parameter:

Why must ground current inrush restraint timesetpoints be coordinated?

and Ground Current Inrush Restraint Timesetpoints must be coordinated to ensure the switch control has enough time after the time block to detect a real ground fault.

How is fault current measured?

Fault current for each phase is measured by a high-speed detecting circuit with a full scale of approximately 4000 amps RMS and is sampled every 6.25 ms. The control phase fault-detection characteristics are controlled by thePhase Fault-Detection Current Leveland the Phase Fault-Duration Time Thresholdsetpoints. All three phase currents are monitored and compared with these two setpoints. When an overcurrent condition is registered, the switch control starts the Phase Fault Duration Time Thresholdtimer. If the overcurrent condition is present for the duration of the timer, the switch control records a Phase Overcurrent Faultstate. To determine the proper setting, look at the source-side device phase time-current characteristic (TCC) curves for the range of fault duty, up to the maximum available phase fault current at the sectionalizing switch. In general, set the Phase Fault Detec - tion Current Levelsetpoint slightly lower than the source-side device’s minimum pickup/trip and the Phase Fault Duration Time Thresholdsetpoint slightly faster than the fastest time the source-side device will trip. For an example, see Figure 1 on page 7. Follow these steps to configure the parameter:

What is time block mode?

Time Blockmode, the Phase Fault Duration Time Thresholdand Phase Current Inrush Restraint Timesetpoints must be coordinated to ensure the switch control has enough time after the time block to detect a phase fault.

Why do you need to coordinate phase current inrush restraint timesetpoints?

Phase Current Inrush Restraint Timesetpoints must be coordinated to ensure the switch control has enough time after the Time Blockperiod to detect a phase fault.

What voltage is used in a S&C 5800 series?

The S&C 5800 Series Automatic Switch Control line voltage input range is 93 to 276 Vac. Failure to observe the precautions below will result in serious personal injury or death.

When does inrush and load pickup current occur?

Inrush and load pickup currents occur when voltage is restored to a distribution circuit with connected load:

What is ground fault protection?

Once again one must look to the definitions in Article 100, where ground-fault protection of equipment is defined as, “A system intended to provide protection of equipment from damaging line-to-ground fault currents by operating to cause a disconnecting means to open all ungrounded conductors of the faulted circuit. This protection is provided at current levels less than those required to protect conductors from damage through the operation of a supply circuit overcurrent device.”

What is a ground fault circuit interrupter?

Article 100 of the NEC defines ground-fault circuit interrupter as, “A device intended for the protection of personnel that functions to de-energize a circuit or portion thereof within an established period of time when a current to ground exceeds some predetermined value that is less than that required to operate the overcurrent protective device of the supply circuit.”

What voltage is required for a service disconnect?

The National Electrical Code is a minimum standard, so we need to do at least that much. With that in mind, one can conclude that GFP is required for all service disconnecting means at the voltage rating of over 150 volts phase-to-ground but not exceeding 600 volts phase-to-phase. Looking a bit further, if we had an electrical service rated at 1600 amperes and 480/277 volts and the “six disconnect” rule were being applied as allowed by Section 230-71, meaning six disconnects rated at 400 amperes each, there would be no requirements for GFP to be installed for the service; installation would be optional. Obviously the system could benefit if a ground-fault protective device were installed as a main disconnect for the service, but this would not be required by the NEC. Ground-fault protection for equipment is required by Section 215-10 for feeder disconnects, 230-95 for service disconnects and in health care facilities, 517-17 for second level protection and coordination where a service disconnect is a ground-fault protective device.

What is GFCI protection?

GFCI protection is required to provide protection against the hazards of electric shock and electrocution. The Underwriters Laboratories (UL) requirements for Class A ground-fault circuit interrupters is that the device will open (trip) when the continuous 60 cycle differential current exceeds 6 mA, but shall not trip at less than 4 mA. One can see by these values of current at which GFCIs operate that these types of protective devices are sensitive to low-level current leakage (see figure 1).

What causes electrical explosions?

An electric arc generating a tremendous amount of heat is readily sustained at these higher voltage levels. Conductive ionized gases produced by these arcs contribute to the electrical explosion and can go from a phase-to-ground fault to a phase-to-phase short circuit and result in destructive magnetic and thermal forces that cause the equipment to literally melt down (see photos 1 and 2). The NEC does not require ground-fault protection for services at voltage levels less than 150 volts phase-to-ground; however, it is permitted to be installed on those services.

Is GFCI protection mandatory?

The requirements in Section 680-6 for receptacle location and GFCI protection was, and still is, a mandatory requirement. As the Code developed over the years, more and more additional requirements for GFCI protection were made mandatory. In the 1999 edition of the NEC, the requirements for GFCI protected circuits and receptacles are widespread and numerous. These devices have certainly contributed to the personnel safety and protection as required by the NEC.

1.Ground-fault Protection of Equipment and Ground-fault …

Url:https://iaeimagazine.org/electrical-inspections/ground-fault-protection-of-equipment-and-ground-fault-circuit-interrupters-2/

18 hours ago  · The maximum operational current setting for these devices is 1200 amperes. The maximum time delay is one second for ground-fault currents equal to or greater than 3,000 …

2.What Are The Maximum Current And Time Delay Settings …

Url:https://gen.aussievitamin.com/what-are-the-maximum-current-and-time-delay-settings-of-ground-fault-protection-as-set-forth-by-the-nec/

21 hours ago The maximum setting of the ground-fault protection shall be 1200 amperes, and the maximum time delay shall be one second for ground-fault currents equal to or greater than 3000 …

3.Ground-Fault Relay Protection Schemes | EC&M

Url:https://www.ecmweb.com/content/article/20892532/groundfault-relay-protection-schemes

12 hours ago The maximum setting for the ground fault relay (or sensor) can be set to pick up ground faults at a maximum of 1200A and actuate the main switch or circuit breaker to disconnect all phase …

4.Understanding Ground Fault and Leakage Current …

Url:https://code-authorities.ul.com/about/blog/understanding-ground-fault-and-leakage-current-protection/

29 hours ago is maintained, the circuit breaker will trip at the prescribed time delay. The time delay setting may be set between the following time delay bounds of 100ms and 500ms, at 50ms steps. …

5.Ground Fault Protection - Eaton

Url:https://www.eaton.com/content/dam/eaton/products/electrical-circuit-protection/fuses/solution-center/bus-ele-tech-lib-ground-fault-protection-requirements-gfp.pdf

26 hours ago  · When determining the circuit breaker ground fault settings for two or more tiers, should there be any consideration for the time gap between the delay settings? For instance, if …

6.Ground-Fault Protection - Schneider Electric

Url:https://product-help.schneider-electric.com/ED/NSX/NSX_MicroLogic5-6-7_Guide/EDMS/DOCA0141EN/DOCA0141xx/NSX_Micrologic567_Protection_Function/NSX_Micrologic567_Protection_Function-17.htm

5 hours ago Zero-sequence current is caused by an unbalanced fault involving ground. Zero-sequence overcurrent elements can be set very sensitive (i.e., a low pickup setting) because the zero …

7.White Paper Ground fault application guide - Siemens

Url:https://assets.new.siemens.com/siemens/assets/api/uuid:9541d253-5b3e-45c6-b94a-58f5171e6c91/sie-wp-wl-groundfaultapplicationguide.pdf

3 hours ago Set the Phase Fault Detection Current Levelsetpoint to a value about 90% of the minimum pickup/trip of the source-side device. STEP 2. Set the Phase Fault Duration Time …

8.Setting delay time for ground fault protection - Mike Holt's …

Url:https://forums.mikeholt.com/threads/setting-delay-time-for-ground-fault-protection.123924/

19 hours ago

9.Application Guidelines for Ground Fault Protection

Url:https://cdn.selinc.com/assets/Literature/Publications/Technical%20Papers/6065_ApplicationGuidelines_Web.pdf

5 hours ago

10.Setting Phase and Ground Overcurrent Levels

Url:https://www.sandc.com/globalassets/sac-electric/documents/sharepoint/documents---all-documents/instruction-sheet-1042-572.pdf

33 hours ago

A B C D E F G H I J K L M N O P Q R S T U V W X Y Z 1 2 3 4 5 6 7 8 9