Grounding bushings for use with conduit fittings, tubing (EMT) fittings, threaded rigid metal and intermediate metal conduit, or unthreaded rigid metal and intermediate metal conduit have provision for the connection of a bonding or grounding wire or have means for mounting a wire connector available from the manufacturer.
What is the purpose of ground bushings?
Grounding bushings provide the electrical continuity required by the NEC at service equipment and for circuits rated over 250 V. They may be used with or without a bonding or grounding conductor as determined by the bonding or grounding function that is intended to be accomplished.
What is the difference between bonding and grounding bushings?
Such a bushing may also have means usually one or more set screws) for reliably bonding the bushing to the metal equipment enclosure or box in the same manner that this is accomplished by a bonding bushing. Grounding bushings provide the electrical continuity required by the NEC at service equipment and for circuits rated over 250 V.
Do I need grounding bushings for a 250V box?
Grounding bushings are also required for the bonding of metal boxes etc. where the voltage exceeds 250 volts and concentric or eccentric KO's are encountered. That is unless the box with the KO's are listed specifically for bonding over 250 volts than they are not required.
Do I need a grounding bushing for 480 3-phase stubbing?
Say a grounding bushing is required on the service side, rigid conduit, no concentrics. Can you use one of these: How about flex carrying 480 3-phase stubbing up from a PVC FA to a transformer? This would be after the service. The way I'm interpreting it is that it wouldn't require a grounding bushing. Click to expand...

Where is a grounding bushing required?
You need a bonding bushing if: Your raceway contains service conductors. Your raceway contains grounding electrode conductors. In fact, you may need one on both ends, for GEC performance.
What is a grounding bushing?
Insulated Grounding Bushings (2-Pack) are designed to ground the wires in threaded rigid or IMC conduits. The bushings are made of heat-tolerant thermoplastic and can be used in indoor or outdoor environments. Insulate wires in threaded rigid or IMC conduits.
Are grounding bushings required?
The National Electrical Code (NEC) Articles 250.64 & 250.92 require the use of a grounding bushing. In addition, NEC Articles 344.46 & 300.4(G) require a bushing with conductors 4AWG or larger.
What is the purpose of a bonding bushing?
Bridgeport's grounding and bonding bushings are used to properly bond and terminate service conduits to a cabinet, box or enclosure. Adjustable lay-in lugs accept and position conductors for simple access during installation. The plastic liner prevents damage to the wire jacket during installation and use.
Are bushings required on PVC conduit?
A bushing is typically NOT required when using PVC conduit.
Can you use EMT as a ground?
Electrical metallic tubing (EMT) is one type of acceptable equipment grounding conductor listed in Section 250.118. When installed properly and the fittings are made up wrench-tight, EMT is an excellent equipment grounding conductor.
Is a ground wire required in metal conduit?
2 Answers. Show activity on this post. Conduit (RMC, IMC or EMT) is an NEC-accepted ground path. So, if the wires are in steel conduit, no OTHER ground wire is required.
At what voltage do I need to install a grounding bushing on concentric knockouts?
Overview. Concentric or eccentric knockouts that are part of a cabinet, cutout box, junction box, or pull box, installed on an electrical system that has a voltage over 250 volts have not been investigated for grounding and bonding, and would therefore require a bonding jumper to be installed.
What is a grounding locknut?
3/4“ grounding locknuts are used on 3/4” threaded conduits or connectors to bond locknuts when additional locking and grounding connections are required, such as when severe vibration is encountered.
How do you use a grounding wedge?
0:000:50How to Use a Grounding Wedge in AC Unit Repair - YouTubeYouTubeStart of suggested clipEnd of suggested clipBut they make them to go up from three quarter inch to six inch. What this does is actually when youMoreBut they make them to go up from three quarter inch to six inch. What this does is actually when you can't get your wires. Off in a old work situation. This can take place of a bonding bushing.
What is a ground lug?
[′grau̇nd ‚ləg] (electricity) A lug that connects a grounding conductor to a grounding electrode.
What is the grounding electrode conductor?
Basically, a grounding electrode is a conductive object that establishes a direct connection to the earth or ground. The important part is that a grounding electrode has direct contact with ground. There are lots of conductive objects within a structure, however, not all of them establish a direct connection to ground.
What are the two situations where grounding bushings are required?
The most common two situations where grounding bushings are required are: 1. Concentric KO's where voltage to ground is over 250V. 2. Metal pipe containing service conductors. Basically if it's a service use the grounding bushings. Click to expand... .......on the service conductor riser...... if using locknuts.
What is a bonding bushing?
A bonding bushing is a possible method to maintain electrical continuity but not the only way. Reducing washers are listed for grounding and bonding above and below 250 volts to ground.The UL Whitebook states: So I can use reducing washers around concentric and eccentric knockouts without using a bonding bushing.
What is EGC pipe?
EGC can be any metal pipe that is continuous if along that pipe line you enter into a plastic man hole you need to bond all those conduits together!!! Capesci!! Click to expand... There is no general requirement for pipes over 1 1/4" to have plastic bushings.