what is nameplate rpm

by Marion Murray Published 1 year ago Updated 1 year ago
image

RPM (Speed)
The RPM listed on the nameplate is the shaft speed for the motor. The speed of the motor is directly related to the frequency of the line voltage and the number of poles in the motor. At 60 Hz, a 4 pole motor will rotate at approximately 1800 RPM (7200/4 poles).
Mar 20, 2014

What does the RPM on the motor nameplate mean?

 · What is nameplate RPM? The speed at which rated full-load torque is delivered at rated power output is full-load speed. It is generally given as “RPM” on the nameplate. This speed is sometimes called “slip” speed or actual rotor speed …

Do all motor manufacturers stamp all information on the nameplate?

Revolutions Per Minute (RPM) The nameplate includes the based speed given in RPM. Base speed is where the motor develops rated horsepower at rated voltage and frequency. Base speed indicates how fast a fully-loaded output shaft will turn the connected equipment when proper voltage and frequency is applied.

What does CT and VT mean on a motor nameplate?

Revolutions Per Minute (RPM) The nameplate includes the based speed given in RPM. Base speed is where the motor develops rated horsepower at rated voltage and frequency.

Why is it important to understand the terms listed on nameplates?

The line frequency rating of a motor is abbreviated on the nameplate as CY or CYC (cycle), or Hz (hertz). A cycle is one complete wave of alternating voltage or current. Hertz is the unit of …

image

What does nameplate RPM mean?

Revolutions Per MinuteRevolutions Per Minute (RPM) The nameplate includes the based speed given in RPM. Base speed is where the motor develops rated horsepower at rated voltage and frequency. Base speed indicates how fast a fully-loaded output shaft will turn the connected equipment when proper voltage and frequency is applied.

What does A motor nameplate mean?

The common language of the motor nameplate enables installers, operators and maintenance personnel to understand and recognize the type of motor and that motor's requirements quickly and easily. The nameplate defines a motor's basic mechanical design, electrical performance and dimensional parameters.

What is nameplate current?

Current indicated on the nameplate corresponds to the rated power output together with voltage and frequency. Current may deviate from the nameplate amperes if the phases are unbalanced or if the voltage turns out to be lower than indicated. Current on nameplate.

What is nameplate rating?

Nameplate rating means nominal voltage (V), current (A), maximum active power (kWac), apparent power (kVA), and reactive power (kvar) at which a DER is capable of sustained operation.

What is rated RPM of motor?

What Is the RPM of a Motor? RPM is a measurement used to describe a motor's speed. It stands for revolutions per minute and describes the rate at which the rotor is revolving, which is the number of times the rotor shaft completes a full rotation each minute.

How do you read a motor nameplate?

RPM (Speed) The RPM listed on the nameplate is the shaft speed for the motor. The speed of the motor is directly related to the frequency of the line voltage and the number of poles in the motor. At 60 Hz, a 4 pole motor will rotate at approximately 1800 RPM (7200/4 poles).

What is the difference between LRA and FLA?

FLA: Full-Load Amps: Amount of amperage drawn when motor is working at rated horsepower. RLA: Running-Load-Amps: Same as FLA. LRA: Lock-Rotor-Amps: A motor draws a surge of amperage when it starts to get the rotor rotating and to achieve the rated horsepower.

What is CC on a motor nameplate?

CC – Certified Compliant # This number appears on all motors that require compliance with US energy law.

What is min 1 on a motor nameplate?

Full Load Speed (RPM) Full-load speed is the speed at which rated full-load torque is delivered at rated power output, this speed is sometimes called slip-speed or actual rotor speed. In the example nameplate, this is declared as min-1, but generally it is declared in RPM; both these measurements are the same.

What is nameplate MW?

Nameplate capacity is the theoretical output registered with authorities for classifying the unit. For electric power stations, the power output is expressed in Megawatt electrical (MWe). For fuel plants, it is the refinery capacity in barrels per day.

What is nameplate energy?

Each power plant or generating facility has a “nameplate capacity” which indicates the maximum output that the generator can produce. For example, if XYZ Power Plant has a nameplate capacity of 500 megawatts, it means the plant is capable of producing 500 megawatts operating at continuous full power.

How is nameplate capacity calculated?

The formulas we use is: Nameplate Capacity (kW) = (Percent of Building Load * Annual Building Load (kWh)) / (8760 * Capacity Factor ).

What do the numbers on an electric motor mean?

The number of turns indicates how much wire is wrapped inside the motor. A higher turn number means more wire and thus more resistance, resulting in a slower motor. So turns with a lower number means a faster motor. The turn rating is inversely proportional to the power generated by the motor.

What do motor frame numbers mean?

The frame number relates to the “D” dimension (distance from center of shaft to center bottom of mount). For example, in the two-digit 56 frame, the “D” dimension is 3½”, 56 divided by 16 = 3½”.

Which of the following information is available on nameplate of a motor?

The NEC states that the motor nameplate must show the following information: Rated voltage or voltages. Rated full-load amps for each voltage level. Frequency.

What is the Y on a motor nameplate?

AC Motor Name Plate - Terms & MeaningsName Plate TermsMeaningNEMA Nom. EfficiencyMotor operating efficiency at full load.PHSpecifies number of stator phases of the motor.PoleSpecifies number of poles of the motor.YSpecifies whether the motor windings are Star (Y) connected or Delta (Δ) connected.12 more rows

What is a FLA nameplate?

The nameplate FLA is a very important rating that is used to select the correct wire size, motor starter, and overload protection devices necessary to serve and protect the motor. For a multispeed motor, the full-load current is only listed for the maximum speed.

What is the tolerance for voltage above and below the rated nameplate value?

Indicates the operating voltage required for optimal performance as intended by the motor manufacturer. Rotating machines are typically designed with a 10% tolerance for voltage above and below the rated nameplate value.

What is shaft horsepower?

Shaft horsepower is a measure of the motor’s mechanical output rating. Expressed as its ability to deliver the torque required for the load at rated speed.

How to calculate slip in motor?

To calculate motor slip in terms of percentage, subtract the asynchronous speed from the synchronous speed, then divide by the synchronous speed and multiply by 100.

What is rated full load speed?

The rated full load speed is the actual RPM value listed on the motor nameplate. The term "slip" refers to the difference between the synchronous speed and actual full load speed (also referred to as the asynchronous or slip speed).

What is the synchronous speed of a four pole motor?

A four pole motor with no load connected, for example, would have a synchronous speed of 1,800 RPM at 60Hz and a synchronous speed of 1,500 RPM at 50 Hz. If a motor is designed to operate at different speeds when controlled by a variable frequency drive (VFD), the input frequency range must be displayed on the nameplate.

What are some examples of electric motors?

Children's toys, vacuum cleaners, fans, power tools, electric vehicles, mechanical pumps, elevators, and freight trains are just a few examples of the wide range of applications where you will find some form of electric motor. Magnetic fields created by electrical charges are the driving force behind motors which generate the torque required to perform useful work.

What is the nameplate information of a motor?

Nameplate information gives the auditor a snapshot understanding of several important operating limits. For example, if the motor’s nameplate Full Load Amps (FLA) is 45 and the auditor measures 50, then excessive Amp-pull or load is highly likely. Alternatively, if 15 Amps on a 45 FLA motor is measured, the motor is very under-loaded and operating inefficiently. Significant deviations in measured operating levels from nameplate information identify specific problem areas.

Why is it important to know the terms on a nameplate?

Basic knowledge of the terms listed on a nameplate allows the auditor to better understand the performance limits of the motor and gear drive, as well as their combined efficiency. The purpose of this Fact Sheet is to explain the meaning and purpose of nameplate information and show how to use nameplate and measured motor speed to calculate motor loading.

What is a gear drive?

Gear drives play an important role in agricultural machinery. Prior to variable speed drives, changing drive-to-driven gear or pulley ratios was the only way to vary delivery shaft speed and torque. Gear drives are not only used to transmit and vary both, but also to alter power delivery orientation (angle). For example, a right-angle gear drive transposes power from a horizonally-mounted motor to the vertical driveshaft of a turbine pump.Gear drives have nameplates that are not as detailed as an electric motor. Figures 5 and 6 illustrate this fact.

What is a TEFC motor enclosure?

In contrast, a TEFC motor enclosure is totally enclosed and comes with an external cooling fan. Proper selection of the motor enclosure is very important because it must provide around-the-clock protection, regardless of the situation. TEFC motors are typically found on irrigation sites because they are designed to work outdoors. A TEFC enclosure also is required when explosive vapors are present.

What is the frame size of a motor?

Fractional sizes include 42, 48 and 56; whereas, 140, 180 and larger are integral type motors. If a new motor’s frame size differs from the old motor, it might not properly fit.

What is a Hz motor?

The abbreviation Hz is the Hertz or input voltage frequency of the motor. Motor speed is directly related to the line input voltage frequency. In the U.S., 60 Hz is the standard frequency while 50 Hz is common elsewhere.

What does FLA mean in motors?

FLA is an abbreviation for the Full Load Amp rating. Motors are designed to operate at 50 to 100 percent of their rated load. At FLA, the motor runs at 100 percent of its rated load and the label specifies the current it will draw.

Voltage and frequency ratings

NEMA (voltage variation). The tolerance for voltage variation under running conditions in NEMA Std. MG 1, 12.44, is ±10% of rated voltage at rated frequency.

Current ratings

NEMA. The clause regarding motor current rating in NEMA Std.

Speed (rpm) ratings

NEMA. NEMA Std. MG 1, 12.46 allows a seemingly liberal tolerance for full-load speed variation to account for differences in manufacturing processes and materials among motors with identical ratings.

Efficiency ratings

NEMA. Per NEMA Std. MG 1, 12.58, full-load efficiency shall be not less than the minimum value associated with the nominal efficiency when a motor is operating at rated voltage and frequency. The nominal efficiency rating is identified on the nameplate by the caption “NEMA Nominal Efficiency” or “NEMA Nom.

Putting it all together

The Table summarizes the IEC and NEMA tolerances discussed in this article. Use caution when interpreting and assessing motor performance versus nameplate ratings, especially when it involves voltage, frequency, current, speed (rpm), and efficiency.

What is the nameplate of a motor?

The nameplate lists the maximum ambient temperature at which the motor can operate and still be within the tolerance of the insulation class at the maximum temperature rise. It is often abbreviated as "AMB" on the nameplate.

What does "time rating" mean on a motor?

Time rating or duty specifies the length of time the motor can operate at its rated load safely and indicates whether the motor is rated for continuous duty. This is shown as "CONT" on the nameplate.

What is the IEC code for a motor?

However, where NEMA designations are in words, such as Open Drip Proof or Totally Enclosed Fan Cooled, the IEC uses a two-digit "Index of Protection" code to describe how well the enclosure protects the motor from the environment. The first digit indicates how well protected the motor is against the entry of solid objects, the second digit refers to water entry. The two digit number is followed by letters “IP”.

What is SF in motor service?

Motor Service Factor (SF) is the percentage of overloading the motor can handle for short periods when operating normally within the correct voltage tolerances. This is practical as it gives you some 'fudge' in estimating horsepower needs and actual running horsepower requirements. It also allows for cooler winding temperatures at rated load, protects against intermittent heat rises, and helps to offset low or unbalanced line voltages. For example, the standard SF for open drip-proof (ODP) motors is 1.15. This means that a 10-hp motor with a

What is rated load speed?

The rated full load speed, or rpm (revolutions per minute) of a motor is the speed at which the motor will operate under full torque conditions when applied voltage and frequency are held constant at the rated values.

What is full load amperage?

When the full-load torque and horsepower is reached , the corresponding amperage is known as the full-load amperage (FLA). This value is determined by laboratory tests; the value is usually rounded up slightly and recorded as the nameplate value. Rounding up allows for manufacturing variations that can occur and some normal voltage variations that might increase the full-load amps of the motor. The nameplate FLA is used to select the correct wire size, motor starter, and overload protection devices necessary to serve and protect the motor.

What is NEMA type?

NEMA requires a manufacturer's type, but there is no industry standard for what this is. It is sometimes used to define 1- or 3-phase; single or multi-speed; construction, etc. The "type" definition varies from manufacturer to manufacturer.

image

1.How to Read a Motor Nameplate | VFDs.com

Url:https://vfds.com/blog/how-to-read-a-motor-nameplate

17 hours ago  · What is nameplate RPM? The speed at which rated full-load torque is delivered at rated power output is full-load speed. It is generally given as “RPM” on the nameplate. This speed is sometimes called “slip” speed or actual rotor speed …

2.Motor Nameplate and Ratings Explained - TestGuy

Url:https://testguy.net/content/367-Motor-Nameplate-and-Ratings-Explained

3 hours ago Revolutions Per Minute (RPM) The nameplate includes the based speed given in RPM. Base speed is where the motor develops rated horsepower at rated voltage and frequency. Base speed indicates how fast a fully-loaded output shaft will turn the connected equipment when proper voltage and frequency is applied.

3.Understanding Motor and Gear Drive Nameplate …

Url:https://extension.okstate.edu/fact-sheets/understanding-motor-and-gear-drive-nameplate-information-for-irrigation-pump-evaluations.html

4 hours ago Revolutions Per Minute (RPM) The nameplate includes the based speed given in RPM. Base speed is where the motor develops rated horsepower at rated voltage and frequency.

4.How Precise Are Motor Nameplate Ratings? | EC&M

Url:https://www.ecmweb.com/maintenance-repair-operations/motors/article/20897647/how-precise-are-motor-nameplate-ratings

25 hours ago The line frequency rating of a motor is abbreviated on the nameplate as CY or CYC (cycle), or Hz (hertz). A cycle is one complete wave of alternating voltage or current. Hertz is the unit of …

5.Understanding Motor Nameplate Information: NEMA …

Url:https://www.cedengineering.com/userfiles/Understanding%20Motor%20Nameplate%20Information-R1.pdf

2 hours ago The rated full load speed, or rpm (revolutions per minute) of a motor is the speed at which the motor will operate under full torque conditions when applied voltage and frequency are held …

6.DC Motor rpm on nameplate - Eng-Tips Engineering Forums

Url:https://www.eng-tips.com/viewthread.cfm?qid=357922

3 hours ago  · Now just run the motor on the Dc field weakening control drive of your choice, up to 1400rpm with a solid 2.00amps dc on the field winding. You should then be able to measure …