Knowledge Builders

what is the proper superheat and subcooling

by Lempi Schulist Published 2 years ago Updated 2 years ago
image

Superheat and Subcooling Defined

  • Superheat is defined as the amount of heat added to a vapor above its boiling point.
  • S ubcooling is defined as the amount of heat removed from a liquid below its condensing point.

“Typically” on TXV systems the Superheat will range between 8 to 28 degrees with a target of about 10 to 15 degrees. The Subcool range on TXV systems will range from about 8 to 20. Although this is not enough information to charge a system, it does give a technician a better understanding of the systems operation.Jul 1, 2015

Full Answer

How is superheating and subcooling done?

Subcooling here serves itself from the superheating and vice versa, allowing heat to flow from the refrigerant at a higher pressure (liquid), to the one with lower pressure (gas). This creates an energetic equivalence between the subcooling and the superheating phenomena when there is no energy loss. Normally, the fluid that is being subcooled ...

How do you calculate degrees of superheat?

How do you calculate degrees of superheat? The total superheat calculation is as follows: Degrees compressor in temperature (50 degrees) minus saturation temperature (23 degrees) equals total superheat (27 degrees). In the above example, the total superheat was calculated to be 27 degrees.

How to calculate superheat temperature?

Calculating superheat: Measure the low-side pressure with your gauge. Convert pressure to temperature with an app, slide or chart. Next, take the temperature of the suction line where it leaves the condensing unit, though stay 4-6 inches from the compressor. Use your measurements to determine the amount of superheat.

How to calculate superheat R22?

How to calculate superheat R22? The superheat in the system with R22 is calculated by the following equation. Total Superheat with R22 = Corresponding temperature at suction pressure – Temperature measured at a suction line or outlet of the evaporator. The superheat is nearby 10 ° F in most cases.

image

What is proper superheat?

Superheat for most systems should be approximately 10F measured at the evaporator; 20°F to 25°F near the compressor. If the suction pressure is 45 psi, (which converts to 22°F) and the suction temp is 32°F, the system still has 10°F of superheat.

What is a good target superheat?

The minimum recommended target superheat for most charts is between 4F to 5F for the environments with low indoor wet bulb and high outdoor dry bulb.

What is the proper subcooling?

Generally speaking, 10-12° of subcooling at the outlet of the condenser coil is most common. However, you must look for the proper design subcooling for the particular system you are working on. Some systems will require subcooling readings of up to 16° for maximum efficiency and capacity.

What is the rule of thumb for superheat and subcooling?

The general rule of thumb is that it should give up about 10 degrees before it leaves the condenser coil. If your system is working properly, the liquid temperature leaving the coil should be 105 degrees.

What are good numbers for superheat and subcooling?

“Typically” on TXV systems the Superheat will range between 8 to 28 degrees with a target of about 10 to 15 degrees. The Subcool range on TXV systems will range from about 8 to 20. Although this is not enough information to charge a system, it does give a technician a better understanding of the systems operation.

Is lower superheat better?

“Higher than proper superheat results in low system capacity and compressor overheating,” Orr explained. “Low or zero superheat can result in compressor flooding and damage.” He added that there is no such thing as negative superheat because superheat simply indicates that the refrigerant is fully vapor.

What happens if superheat is too high?

Too high of a superheat can cause the heat of compression to increase, causing the temperature at the discharge valves to increase. If the temperature increases beyond its safe operating temperature, it will cause damage to the compressor.

What happens if superheat is too low?

A low or zero superheat reading indicates that the refrigerant did not pick up enough heat in the evaporator to completely boil into a vapor. Liquid refrigerant drawn into the compressor typically causes slugging, which can damage the compressor valves and/or internal mechanical components.

What is the superheat temperature?

Superheat is a measurement of the temperature a vapour is above its saturation or boiling point. Superheat can be measured in any vapour such as steam or refrigerant. There are two important superheat readings that can be taken on a system.

Is a 20 degree superheat good?

It is recommended that all TXV-controlled refrigeration systems have at least 20 degrees of compressor superheat to ensure that the compressor will not see liquid refrigerant (flood or slug) at low evaporator loads.

What is the formula for superheat?

5:5811:43How to Read SUPERHEAT and SUBCOOLING - YouTubeYouTubeStart of suggested clipEnd of suggested clipMinus the line temperature so gauge minus line will equal my sub cooling reading and for the superMoreMinus the line temperature so gauge minus line will equal my sub cooling reading and for the super heat. It would be l minus g equals sh and that was like my little cheat sheet. So on this one it's

What is the formula for subcooling?

Calculate the subcooling as follows: subcooling = CT – T. For a refrigerant blend use the saturated liquid (bubble) temperature as the condensing temperature. Subcooling will not usually occur in the condenser unless liquid backs up in the condenser.

How do you determine target superheat?

To determine the Target Superheat for an air conditioning system with a fixed orifice (such as a piston or capillary tube) measure the indoor WB (wet bulb) temperature with a digital psychrometer and the outdoor DB (dry bulb) temperature with a standard digital temperature reader.

What should superheat be with a TXV?

The typical TXV comes factory set for 8-12 degrees of evaporator superheat, which in most cases should be fine. What is the correct setting for evaporator superheat? While it is true lower superheat will make the evaporator more efficient, we need to be more concerned with the compressor or total superheat.

What should my superheat be 410a?

Most heating and cooling systems should operate at a superheat of 10F at the evaporator and between 20F to 25F at the compressor. if your HVAC system has a thermostatic expansion valve (TXV), the subcooling should be between 10F and 18F.

What should superheat be with a piston?

Total Superheat Method (Fixed Orifice / Piston / Capillary Tube / Non-TXV) Temperature must be above 55°F outdoors and above 70°F indoors with a indoor wet-bulb temperature above 50°F The evaporator coil cannot operate below freezing or an overcharge and possible compressor damage could result.

How to check subcooling range?

Using Table 3, you can check the range of Subcooling by taking a wet bulb reading at the evaporator and a dry bulb reading from the air entering the condenser. This check will determine if your Subcooling calculation falls within a proper range. This chart should only be used if the manufacturer's recommendations are not available.

What is subcooling in a condenser?

Subcooling is the amount of liquid held back in the condenser. This allows the liquid to expel heat below saturation pressure=temperature. For every 1° of Subcooling at the same condensing pressure, capacity will increase 0.5%. Increasing Subcooling with an increase of discharge pressure and compression ratio decreases capacity. Add 5° of Subcooling for every 30 ft of liquid line lift. Liquid Subcooling is normally measured at the liquid line service valve. It's usually between 8°F and 12°F.

How to check refrigerant temperature?

2. Take a pressure reading of the suction line at the evaporator to get refrigerant saturation pressure=temperature. The refrigerant saturation pressure=temperature is when the refrigerant is turning from a liquid to a vapor.

Which method is most effective when the indoor conditions are within desired indoor comfort conditions?

Condenser Superheat Method : This method, similar to Evaporator Superheat Method, is most effective when the indoor conditions are within desired indoor comfort conditions or as a secondary method when the evaporator service port is not available. 1.

What is the difference between a liquid line temperature and a saturated condensing temperature?

The difference between the liquid line temperature and the saturated condensing temperature is Subcooling.

Where to find charging chart for condenser?

Sometimes these charts are available from the unit's distributor, manufacturer's web site or installation/service manuals. Most of the time they are glued inside the condenser's service panel. The charts will require an indoor wet bulb temperature reading as well as an outdoor dry bulb temperature reading.

Does latent heat affect temperature?

Latent heat does not affect the temperature. The sum of the sensible and latent heat of the air is called enthalpy or total heat. Cross referencing the indoor wet bulb and outdoor dry bulb temperatures, the charging chart will recommend the proper suction Superheat.

What is superheat and subcooling?

Superheat and Sub-cooling - In HVAC refrigeration coils and fans are used for air conditioners and heat pumps to transfer heat in one direction or another. A good HVAC technician is well versed in refrigeration. Refrigeration is defined as moving heat from one place to another. Modern air conditioners and heat pumps use a chemical refrigerant used in vapor compression refrigeration.

Why is it important to understand superheat and subcooling?

It is very important that a technician understand superheat and sub-cooling as it relates to the function of refrigeration. For the apprentice or the up-and-coming student technician, it is important to study these concepts and practice them in the real world. In the real world as it relates to air conditioners and heat pumps.

What is sub-cooling?

Sub-cooling is the opposite of superheat. In reference to refrigeration for air conditioners or heat pumps, sub-cooling will be the measured amount of temperature of the refrigerant after it has changed state from a vapor to a liquid in the condensing unit. For example, if the temperature of the refrigerant was 110 degrees Fahrenheit when it condensed as the refrigerant moved through the condenser more heat was removed from the liquid than the temperature at which the refrigerant was when it condensed from a vapor into a liquid. So when the refrigerant leaves the condenser if it is 95 degrees Fahrenheit it can be said that there are 15 degrees of sub-cooling.

What is superheat in refrigeration?

Superheat is the amount of heat the refrigerant holds above the temperature at which the refrigerant changed state from a liquid to vapor or gas. A good relational example would be steam. Water will change state to steam (vapor) when it is boiled at 212 degrees Fahrenheit at sea level.

What does a HVAC technician need to know about refrigerant?

Whenever an HVAC technician needs to add refrigerant to a system or adjust the charge the tech needs to know what superheat and/or sub-cooling is to properly ensure the refrigerant charge is correct. It is also important to have a pressure-temperature or PT Chart to properly read the pressures and temperatures.

How far does a condensing unit run?

Most condensing units come pre-charged with refrigerant and depending on the manufacturer the charge in the condenser will take into account the evaporator coil and a line-set run of 25 to 50 feet. This makes it easy for the HVAC installation technician when installing new HVAC equipment as it is easy to make the refrigerant charge adjustment after installation based on the length of the line set. Another charging method sans the superheat and sub-cooling methods is to weigh the charge is based on what the manufacturer recommends for the proper charge.

What is the term for moving heat from one place to another?

Refrigeration is defined as moving heat from one place to another. Modern air conditioners and heat pumps use a chemical refrigerant used in vapor compression refrigeration. This chemical refrigerant has great properties for absorbing heat.

Checking Superheat

Lets pretend you are in front of a condensing unit and have your gauges hooked up, and a temperature clamp (YES you need to BUY one) attached to the bare copper suction line. You record the following information from the low side gauge:

Checking Subcooling

Lets pretend you are in front of the same condensing unit and have your gauges hooked up, and a temperature clamp (YES you still need to BUY one) attached to the bare copper liquid line. You record the following information from the high side gauge:

What is superheat in refrigeration?

Superheat is then any temperature of a gas above the boiling point for that liquid. When a refrigerant liquid boils at a low temperature of 40 degrees in a cooling coil and then the refrigerant gas increases in temperature, superheat has been added. If this refrigerant changed from a liquid to a gas or vapor at 40 degrees and then ...

What are the three types of superheat?

Superheat. Most materials can exist in three forms: solids, liquids, and gases. Water is a common example. Water can exist as a solid (ice), a liquid, or a gas or vapor (steam). Only a gas or vapor (these are interchangeable terms) can be superheated. Let's use water as an example as we explain these terms.

What is latent heat?

Recalling that latent heat is the heat which is added to a liquid to cause it to change from a liquid to a gas (boiling) without a change in temperature, let's go to the next step. When a gas or vapor is above its boiling point, it is said to be superheated. Cooling the gas removes its superheat. When all the superheat is removed from a gas, the gas will condense back into a liquid. The heat removed from a saturated gas to allow it to condense back into a liquid is once again latent or hidden heat and is not a sensible heat process. That is, during the process of changing from a gas to a liquid, it occurs at a constant temperature; therefore a thermometer will not detect any temperature change. That is latent heat.

What temperature is a refrigerant at?

Refrigerant that has boiled (turned into a vapor) at 40 degrees has a saturation temperature of 40 degrees. If the refrigerant vapor is heated to 41 degrees it is no longer saturated, it is then superheated by 1 degree. Remember, only a gas or vapor can be superheated. Superheat is any temperature of a gas or vapor above its saturation temperature.

What is a superheated gas?

If a liquid refrigerant boils at -10 degrees and is then warmed up to 0 degrees, it is then a superheated gas containing 10 degrees of superheat.

What happens when water boils at 212 degrees?

When heated to 212 degrees F, the molecules that make up water are moving at a high enough speed that they overcome the air pressure above the water. As additional heat is added to liquid water at 212 degrees, the water begins to boil. As the water boils it is changing state from a liquid to a gas.

What is the temperature of steam?

After all the water has changed to a gas or vapor (steam), then the addition of still more heat to the vaporized water or steam will cause the temperature of the steam to increase above its boiling temperature of 212 degrees. Any increase in temperature of the steam above its boiling point is called "superheat." Steam at 213 degrees F is superheated by 1 degree F.

How to increase subcooling?

Add refrigerant to increase subcooling. Recover refrigerant to reduce subcooling. Note that if the subcooling and superheat are correct, and the suction pressure is low, the system probably has low air flow. Correct the airflow problem and check the charge again.

Why is liquid subcooling required?

Liquid sub-cooling is required so that you have only liquid entering the expansion valve with no bubbles present. Vapor bubbles present in the refrigerant will cause low refrigerant flow. Low refrigerant flow will cause a loss of capacity and efficiency in a cooling system. Liquid sub-cooling is normally measured at the liquid line service valve. ...

What determines the performance of a heat pump?

Proper performance of heat pumps and air conditioners are determined by many factors, but chief among them is proper refrigerant charge

Why not use suction port on heat pump?

Do not use the common suction pressure port on a heat pump because the pressure drop through the reversing valve will affect the pressure reading. Take the pressure reading and use a temperature-pressure chart to convert that reading to the saturated temperature of the refrigerant that the system uses. Note that most gauges have the commonly used ...

What is the difference between the liquid line temperature and the saturated condensing temperature?

The difference between the measured liquid line temperature and the saturated condensing temperature is the liquid subcooling. Add refrigerant to increase subcooling. Recover refrigerant to reduce subcooling.

How to measure liquid subcooling?

To measure liquid subcooling, attach your gauge manifold to the liquid line service port. If you use a quick-connect fitting on the end of your hose, make sure it’s a low-loss fitting. I’ve seen some quick-connect fittings that allow pressure loss, which can cause inaccuracies in the charging procedure.

Can you overcharge a compressor?

You don’t want to overcharge the system if your thermometer or gages are not perfectly accurate. Overcharging can damage the compressor and will also reduce both the capacity and efficiency of the system. Note that if the suction superheat is correct and the suction pressure is low, the system probably has low airflow.

How cold can a refrigerator superheat?

Some ice machines and other specialty refrigeration may be as low as 3°F of superheat. When setting the superheat on a refrigeration system with any type of metering device, you often must get the case/space down close to the target temperature before you can make fine superheat adjustments.

What is superheat in refrigeration?

First, what is superheat anyway? It is simply the temperature increase on the refrigerant once it has become fully vapor. In other words, it is the temperature of a vapor above its boiling (saturation) temperature at a given pressure.

What does it mean when the superheat is higher?

In other words, a higher superheat means a lower percentage of the coil is being fed with saturated (boiling) refrigerant.

Why does suction pressure drop on a TEV?

You will also notice that the suction pressure will drop when there is less airflow (or fluid flow) over the evaporator coil. However, as the heat load on the coil drops on a TEV/EEV system, the valve will respond and shut further, keeping the superheat fairly constant.

What does it mean when the suction superheat is lower?

In other words, lower superheat means that saturated refrigerant is feeding a higher % of the coil. When the superheat is higher, we know that the saturated refrigerant is not feeding as far through the coil.

Why measure superheat?

Measuring superheat along with suction pressure gives us the confidence that the compressor will be properly cooled. This is one reason why a properly sized metering device, evaporator coil, and load-to-system match must be established to result in an appropriate superheat at the compressor.

How to tell if air is superheated?

How can you tell that the air around us is all superheated? Because the air all around us is made of vapor. If the air around us were a mixture of liquid air and vapor air, first off, you would be dead, and secondly, the air would be at SATURATION. So, the air around us is well above its boiling temperature (-355 ° F) at atmospheric pressure, which means it is entirely vapor and SUPERHEATED. In fact, on a 75-degree day, the air around you is running a superheat of 430°.

What does it mean when a refrigerant is high subcooling?

High Subcooling is an indication that more than the designed amount of refrigerant is “backing up” or “packed” into the condenser. This can be caused by overcharge, restriction (such as a contaminated line drier or kinked liquid line), or an undersized or failing closed metering device.

How much subcooling is needed for a condenser?

Generally speaking, 10-12° of subcooling at the outlet of the condenser coil is most common. However, you must look for the proper design subcooling for the particular system you are working on. Some systems will require subcooling readings of up to 16° for maximum efficiency and capacity.

What does zero subcooling mean?

Zero Subcooling means that the refrigerant in the liquid line is a mix of liquid and vapor; this is not an acceptable condition EXCEPT in cases where the system is designed to inject discharge gas into the liquid line on purpose to increase liquid pressure (headmaster).

Why is subcooling reading in range?

This is often because the previous tech simply “set the charge” by subcooling without fully testing all aspects of the equipment, such as airflow.

What is subcooling on a TXV?

Many techs will say that subcooling is how you “set a charge” on a TXV/TEV/EEV metering device system.

What is subcooling in chemistry?

Subcooling is a measurement of temperature DECREASE of a liquid below its saturation (mixed liquid/vapor) temperature at a given pressure.

What does "at saturation" mean in HVAC?

When we say "at saturation" or "saturated" in the HVAC/R trade, we are generally referring to the refrigerant that…. When we say that there is "flash gas" at a particular point in the system, it can either be a bad thing or a good thing, depending on where it is occurring. Flash gas is just another term for boiling.

How to check subcooling range?from hvacasap.com

Using Table 3, you can check the range of Subcooling by taking a wet bulb reading at the evaporator and a dry bulb reading from the air entering the condenser. This check will determine if your Subcooling calculation falls within a proper range. This chart should only be used if the manufacturer's recommendations are not available.

How to calculate evaporator superheat?from lambdageeks.com

The evaporator superheat calculation remains the same as in the refrigerator.

How to calculate superheat in a freezer?from lambdageeks.com

The calculation of the superheat in the freezer is similar to the refrigerator .

How to calculate superheated steam temperature?from lambdageeks.com

The superheated steam is generally generated in the higher pressure boiler.

What is the best method to charge a refrigerant meter?from hvacasap.com

The Evaporator Superheat Method should be the first effective method of properly charging a fixed refrigerant metering system. The Condenser Superheat Method is ideal when the indoor temperatures are close (+- 5°F) to desired comfort levels would be during that particular season (Heating or Cooling).

What is subcooling in a condenser?from hvacasap.com

Subcooling is the amount of liquid held back in the condenser. This allows the liquid to expel heat below saturation pressure=temperature. For every 1° of Subcooling at the same condensing pressure, capacity will increase 0.5%. Increasing Subcooling with an increase of discharge pressure and compression ratio decreases capacity. Add 5° of Subcooling for every 30 ft of liquid line lift. Liquid Subcooling is normally measured at the liquid line service valve. It's usually between 8°F and 12°F.

Which method is most effective when the indoor conditions are within desired indoor comfort conditions?from hvacasap.com

Condenser Superheat Method : This method, similar to Evaporator Superheat Method, is most effective when the indoor conditions are within desired indoor comfort conditions or as a secondary method when the evaporator service port is not available. 1.

image

1.Superheat and Subcooling: How to Measure Them

Url:https://allthingshvac.com/superheat-and-subcooling

17 hours ago Web · Any Heat that is added to the steam makes it hotter. This is SUPERHEAT...Heat added to a vapor. If we add 5ºF to the steam (213º F) it now has 5º of …

2.Calculating superheat and subcooling for a proper …

Url:https://www.hvacasap.com/hvac-technicians/superheat-subcooling

17 hours ago Web · A TXV should maintain a consistent superheat to keep the proper amount of refrigerant fed to the evaporator. Most TXVs maintain a required superheat of 8° to 12°F. …

3.Videos of What Is The Proper Superheat and Subcooling

Url:/videos/search?q=what+is+the+proper+superheat+and+subcooling&qpvt=what+is+the+proper+superheat+and+subcooling&FORM=VDRE

35 hours ago

4.Superheat and Subcooling Defined - ABR Wholesalers

Url:https://abrwholesalers.com/blog/post/superheat-and-subcooling-defined

28 hours ago

5.Superheat And Subcooling Made Simple | ACHR News

Url:https://www.achrnews.com/articles/94178-superheat-and-subcooling-made-simple

19 hours ago

6.Superheat and Subcooling: The Best Ways to Ensure …

Url:https://www.contractingbusiness.com/archive/article/20865206/superheat-and-subcooling-the-best-ways-to-ensure-proper-refrigerant-charge

4 hours ago

7.What Should My Superheat Be? - HVAC School

Url:https://hvacrschool.com/what-should-my-superheat-be/

26 hours ago

8.UPDATE on Fundamentals of HVAC Superheat

Url:https://www.contractingbusiness.com/service/article/21246682/superheat-subcooling-welcome-fundamentals

26 hours ago

9.What Should My Subcooling Be? - HVAC School

Url:https://hvacrschool.com/what-should-my-subcooling-be/

22 hours ago

10.Superheat and Subcooling Calculator - LennoxPROs.com

Url:https://www.lennoxpros.com/superheat-subcooling-calculator

35 hours ago

A B C D E F G H I J K L M N O P Q R S T U V W X Y Z 1 2 3 4 5 6 7 8 9