
The most common conductor temperature rating is 90°C, but conductors can be rated as low as 60°C or as high as 1,200°C for some special purpose wire and cables.
What is the maximum operating temperature conductors?
The temperature rating for both THHW and XHHW (not XHHW-2) conductors depend on the location where the conductor is installed. With both conductors , if the installed location is a wet location, the maximum operating temperature (or temperature rating) is 75°C (167°F).
Which metal is a bad conductor of temperature?
Since glass is a transparent material with firmly held electrons, it is a bad conductor of heat. The exact reason lies in the science of heat conductivity, where it is explicitly mentioned. Glass is quite reluctant to the flow of electrons.
What does a good thermal conductor mean?
Thermal conductivity. When you heat one side of a material, the other side will warm up. Copper is a good conductor of heat. This means that if you heat one end of a piece of copper, the other end will quickly reach the same temperature. Why air is poor conductor of heat?
How does conductivity of conductor depend on temperature?
The electrical conductivity of semiconductors increases with increasing temperature because, with increase in temperature, number of electrons from the valence bond can jump to the conduction band in semiconductors. What happens when temperature increases in conductor?

What is conductor rating?
Cable ratings determine the parameters within which a cable can be safely used. The most typical cable ratings are temperature, voltage and current. Temperature rating is usually defined as one of the following: - Max conductor temperature rating. - Minimum installation temperature rating.
What does temp rating mean?
It is usually defined as the maximum continuous temperature that the wire can withstand during its lifetime. It is generally limited by the thermal aging characteristics of the polymers, i.e., the plastics used to insulate and/ or jacket the wire.
How does temperature rating impact conductor size selection?
The higher the temperature rating, the greater the ampacity for a given AWG size (gauge) of conductor.
Which conductor has a temperature rating of 90 C?
Type THHN building wireType THHN building wire is a common conductor used throughout the construction industry. This conductor has a maximum operating temperature rating of 90°C.
What temperature can electrical cables withstand?
The CDA research has shown that temperatures of open wires in attics can get perilously close to the 194°F limit. If the wires are buried in attic insulation, pass over light fixtures or, worst of all, are arranged in tight bundles, they get even hotter than if they're out in the open air.
What is the temp of an electrical short?
Generally, these cables also have a short circuit rating which is the highest temperature the cable can withstand during an electrical short circuit lasting up to about half a second. For 90° C rated power cables, the short circuit temperature rating is usually 250° C.
What does 105C mean on a wire?
105C is generally associated with higher voltage conductor.
Why is a temperature limit important for cables?
The minimum continuous flexing temperature is the lowest temperature at which a wire can withstand repeated flexing throughout its lifetime without damage. This rating is especially important for applications in which the wire or cable will be flexed thousands or even millions of times while at very low temperatures.
How do you choose a conductor size?
To calculate the Cable Sizing one needs to divide the voltage running through the cable by the target current. For instance, If your wire has a voltage current of 150 Volts and your target is 30 then you divide 150/30. This gives you your target resistance of 5 which is required.
What does 60 75 mean on a circuit breaker?
60/75°C Wire — All circuit breakers rated 125 A or less are marked for use with 60° C, 60/75°C or 75°C only wire. This marking indicates the proper wire size for termination in accordance with Table 310.15(B)(16) of the NEC .
When would you use a 90 degree cable?
2:363:53Which temperature cable should I use ? - YouTubeYouTubeStart of suggested clipEnd of suggested clipAnd 90 degrees. So it's important to bear this in mind and if you use a 90 degree cable that'sMoreAnd 90 degrees. So it's important to bear this in mind and if you use a 90 degree cable that's intended to operate at 70 degrees i would use the k values for 70 degrees.
Are all breakers rated at 75 degrees?
This is according to the UL standard for circuit breakers, which is summarized as follows: (1) Breakers rated 125 A or less must be marked for use with 60°C, 60/75°C, or 75°C only wire. (2) For breakers rated more than 125 A, the proper wire temperature rating is 75°C and the marking is optional.
What temperature rating sleeping bag should I get?
Winter sleeping bags are available in two varieties—bags with temperature ratings of 0° degrees and those with temperature ratings of -20° or -40° degrees (and occasionally more). For pure winter camping, a person should get a bag with a temperature rating of at least -20° degrees Fahrenheit.
What temp quilt should I get?
A quick way to estimate the comfort temperature of a quilt or bag is to add 10-15°F to the limit temperature. Limit temperature is defined as the lowest temperature at which a person in a curled-up body position is not feeling cold. Hot sleepers, or folks who plan to layer, can look to this number.
Is 98.8 a low-grade fever?
How high a fever is does not necessarily indicate the severity of the illness causing the fever. Temperature between 98.8-100.6 is a low-grade fever and is not considered clinically significant although the patient may feel unwell.
Is 37.5 considered a fever?
An adult probably has a fever when the temperature is above 99°F to 99.5°F (37.2°C to 37.5°C), depending on the time of day.
What is the ampacity of #8 THWN?
That's because #8 THWN is rated 75?C/167?F with an ampacity of only 50.
Can you have conductors at 60C?
The heat dissipation values are quite conservative, and the load calculations are generally quite liberal, so generally one doesn't actually have conductors at 60C, let alone 90C. However some circumstances (conductors embedded in foam insulation, for example) the thermal insulation can be better than the table assumes, and conductor temperatures will be higher.
Is a conductor the same as insulation?
It is really not the conductor so much as the insulation types. Notice for the same size conductor, that different insulation types have different temperature ratings.
Is thermal resistance lower than the table?
In the real world with practical installations, thermal resistance is generally be lower than the tables assume, and thus conductor temperatures will be lower than the tables suggest.
What is the end of life of a polymer?
The end-of-life for polymers is often defined as the point at which the elongation declines to 50 percent because at that point even minor bending of the wire or cable can cause cracking of the insulation, the jacket or both. Every polymer has its own unique thermal aging characteristics.
How does thermal aging affect wire life?
Every polymer has its own unique thermal aging characteristics. However, as a rule-of-thumb, for every 10° C the operating temperature of a polymer is increased, the life is decreased by a factor of two. For example, a wire that is designed to survive 40 years at 90° C would be expected to survive only 20 years at 100° C and 10 years at 110° C. The mathematical model used to calculate the relationship between temperature and cable life is called the Arrhenius relationship [1] after the Swedish chemist that developed it. The Arrhenius relationship coupled with field experience and laboratory aging tests are the basis for the operating temperature rating assigned to most wire and cable products.
What is the temperature rating of wire?
This is the temperature rating that most cable users think of first. It is usually defined as the maximum continuous temperature that the wire can withstand during its lifetime. It is generally limited by the thermal aging characteristics of the polymers, i.e., the plastics used to insulate and/ or jacket the wire. The metallic components of the wire seldom limit the temperature rating except in high-temperature wire where oxidation of the metal begins to become a significant factor at approximately 250° C.
What temperature does a polymer crack?
Depending on polymer type, they begin to crack when bent at temperatures ranging from –10° C down to approximately –80° C. The minimum cold bend rating for wire is usually defined as the lowest temperature at which it can be bent without cracking under specific laboratory conditions. There are several test methods in use by the industry to determine this temperature. They generally involve cooling the wire to a specified temperature (–25° C is typical) and then bending the wire around a mandrel whose diameter is in the range of 4 to 8 times the wire diameter. Details of one such test method are given in Section 7.5 of UL Standard 2556. [2]
How do polymers age?
Most polymers age by gradually becoming brittle over time. One common measure of brittleness is referred to as elongation. This is a laboratory measurement of how much the material can stretch before it breaks. Polymers used in the wire industry typically start life with an elongation in the 300 to 700 percent range depending on polymer type. That is, some polymers can be stretched up to seven times their original length before they break. The end-of-life for polymers is often defined as the point at which the elongation declines to 50 percent because at that point even minor bending of the wire or cable can cause cracking of the insulation, the jacket or both.
How long can a 90°C cable last?
For example, many 90° C rated power cables have an emergency overload rating which permits their use at 130° C for a total of up to 500 hours during their lifetime. Generally, these cables also have a short circuit rating which is the highest temperature ...
Can power cables withstand short circuits?
As a result, cables have been developed that can withstand such overloads.
Table 310.15 (B) (16)
Allowable ampacities of insulated copper conductors rated up to and including 2000 Volts, 60°C through 90°C (140°F through 194°F), Not more than three current-carrying conductors in raceway, cable, or earth (directly buried), based on ambient temperature of 30°C (86°F).
Table 310.15 (B) (17)
Allowable ampacities of single insulated copper conductors rated up to and including 2000 Volts in free air, based on ambient temperature of 30°C (86°F).
Table 310.15 (B) (3) (a)
Adjustment factors for more than three current-carrying conductors in a raceway or cable.
Table 310.15 (B) (2) (a)
For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown above by the appropriate factor shown per the table below.
