what size breaker do i need for a 4500w water heater

by Miss Candace Nienow IV Published 3 years ago Updated 2 years ago

Conclusion. To sum it up, you can either use a 25-amp or 30-amp breaker for a 4,500-watt heater. For wiring, you can choose between a 10-gauge wire or a 10/2 wire for this setup.Jun 2, 2022

Full Answer

What size breaker do I need for a 50 gallon water heater?

Most 50-gallon water heaters have 4500-watt heating elements. As such, 4500 watts divided by 240 volts equals 18.75 amperes. Multiplying 18.75 amperes by 1.25 results in 23.4375 amperes. A 25-amp or 30-amp circuit breaker is ideal.

How many AMPS is a 4500 watt water heater?

The answer to this is the exact figure you get when you convert 4500 watts to amps: 18.75. Since a water heater is a continuous load device, we need to multiply that value further by 125%. The result is 23.4 amps. The right circuit breaker for this appliance with 4500 watts at 240 volts is either 25 amps or 30 amps.

What size wire do I need for a 3000 watt water heater?

You can also install 8-Gauge wiring for a 30-ampere circuit breaker serving a 3000-watt, 120-volt water heater. Here is a helpful table for finding out the circuit breaker sizes and wire gauges for different wattage-rated and voltage-rated water heaters.

How many amps does a water heater use?

Since a water heater is a continuous load device, we need to multiply that value further by 125%. The result is 23.4 amps. The right circuit breaker for this appliance with 4500 watts at 240 volts is either 25 amps or 30 amps.

What size breaker do I need for a 240V 4500 watt water heater?

Step 3 - Calculate the Breaker Size So, following along with our example, multiply 18.75 Amps by 125%. For a 4500 watt 240 volt water heater, you will need a 25 or 30 Amp circuit breaker. The majority of electricians will recommend installing a 30 Amp breaker to allow for electrical fluctuations.

What size breaker is required for a 5500 watt water heater?

Meanwhile, an 80-gallon heater powered by 5500 watts and 240 volts, will result in 5500W/240V x (1.25 continual load) = 28.64 amps. Meaning, a 30-amp dedicated circuit breaker is enough.

Can you run a 5500 watt water heater on a 20 amp breaker?

Since this is a purely resistive load, the breaker is 30 Amps and the wiring is 10 Amps. If the elements are strapped for a draw of 18.75 Amp, permanent draw loads should be sized 80% of the breaker capacity so a 20 Amp breaker is limited to 16 Amp.

What size breaker does a hot water heater take?

30-ampElectric water heaters require a 240-volt dedicated circuit, which serves only the water heater and no other appliances or devices. The circuit wiring typically includes a 30-amp double-pole breaker and 10-2 non-metallic (NM) or MC cable.

How many amps does a 5500 watt water heater pull?

So, 5500 watts / 220 volts X 0.80 = 20 amps.

How many amps is 5500 watts at 240 volts?

In general, a 5500 watt generator provides approximately 45 amps, in case of 120 volts or 23 amps in case of 240 volts.

What size wire should I use for a 40 amp breaker?

840 AMP Wire Size For a maximum of 40 amps, you'll need a wire gauge of 8.

What size breaker do I need for a 3500 watt water heater?

Sizing Water Heater BreakersElement WattsBreaker Size 120vWire Gauge250030 amp14300030 amp123500NA124000NA105 more rows•Jun 17, 2021

What size wire can handle 30 amps?

10-gauge wire“Twelve-gauge wire is good for 20 amps, 10-gauge wire is good for 30 amps, 8-gauge is good for 40 amps, and 6-gauge is good for 55 amps,” and “The circuit breaker or fuse is always sized to protect the conductor [wire].”

What size breaker do I need for a 3000 watt water heater?

For the 3000W unit you have, you will require a 20A double pole breaker (240V) and 12/2 w/ground cable. The NEC requires that the branch circuit supplying a storage type water heaters be rated at not less than 125% of the nameplate rating.

How do you determine breaker size?

To calculate the breaker size, simply divide the adjusted wattage by 240 volts to find the rated amperage needed for your subpanel. Often, the result is not a common circuit breaker size. and you can simply round up to the next higher size of ​the breaker.

What size breaker do I need for a 6000 watt water heater?

If you have a heater that uses a total of 6000 watts in a 240 volt connection, you'll need a minimum of 25 Amps. However, because the system will use all 25 Amps, it's safer to get a circuit breaker of 30 Amps.

What size breaker do I need for a 6000 watt water heater?

If you have a heater that uses a total of 6000 watts in a 240 volt connection, you'll need a minimum of 25 Amps. However, because the system will use all 25 Amps, it's safer to get a circuit breaker of 30 Amps.

What size breaker do I need for a 3500 watt water heater?

Sizing Water Heater BreakersElement WattsBreaker Size 120vWire Gauge250030 amp14300030 amp123500NA124000NA105 more rows•Jun 17, 2021

What size wire should I use for a 40 amp breaker?

840 AMP Wire Size For a maximum of 40 amps, you'll need a wire gauge of 8.

What size wire do I need for a 40 gallon water heater?

The best size wire for a 40 gallon electric water heater is a 12 AWG wire because its energy output capacity nearly matches with what's needed to run a 40 gallon electric water heater.

What Size Breaker for 40 and 80-Gallon Water Heater?

Most families use a tank size of 40 to 80 gallons for a water heater — depending on how much they rely on warm water daily.

What type of breaker is used for a water heater?

An electrical water heater typically uses a 30-amp breaker, so something like the Q230 30-Amp Double Pole Type QP Circuit Breaker will do the work well.

What happens if your water heater breaker is too small?

If the breaker is too small for the water heater’s ampere requirement, expect that your CB will trip continuously. Not only that, too much on and off of the heater can cause internal damage. Do not have your water heater share a circuit with other appliances, and please upgrade the breaker if necessary.

How many amps for a 40 gallon water heater?

With our answer, a 40-gallon water heater needs at least a 25-amp breaker, the closest to the amperage value. However, I highly recommend using 30-amps for a safer breaker size.

How to calculate water heater amp size?

Since you already know the wattage and voltage of your water heater, all you need is to follow the Ampere formula , which is I (amps) = P (watts)/ V (volts).

How many volts should a boiler be?

Voltage- The volts of your boiler plays an integral part in a healthy circuit. You can plug an average heater to a 220 or 240 Volts outlet based on your tank size and wattage.

What type of wire is needed for a 30 amp water heater?

Also, consider your breaker size for water heater. 30-amp circuit breakers, commonly used for a large boiler tank, require a 10-2 non-metallic or MC cable. This type of wire is suitable for start loads of 40-amps and a constant load of 35-amps.

Understanding Your Water Heater

The best way to find your tank specifications is to ask your retailer or the brand manufacturer. You must determine your heater’s size first before determining your breaker’s size. There are three factors you need to consider to ensure safety:

How large is the breakers for 40 and 80-gallon water heaters?

Water heater tanks typically range from 40 to 80 gallons, depending on how much hot water is used every day by a family.

When wiring a water heater, what wire size is best?

If the wiring is incompatible, a water heater can’t be connected to its breaker. Your heater’s amperage must match its wire size. Here are some suggestions:

Circuit breakers: Preventive measures before buying

You must consider the amp difference between the circuit breaker and the heater when choosing the right water heater circuit breaker size. The correct size must be selected. The wrong size or number of breakers can create an electrical hazard.

Frequently Asked Questions (FAQs)

The right circuit breaker for this appliance with 4500 watts at 240 volts is either 25 amps or 30 amps. If the water heater isn’t rated as “continuous load”, then it would have been fine to use 100% of the circuit breaker’s rating

Final Verdict: 4500 Watt Hot Water Heater Breaker Size

Knowing what size breaker to use for a water heater isn’t difficult as long as you gather the right information. You can determine the proper breaker size by understanding the three wire heater elements – voltage, wattage, and wire size.

What Size of Circuit Breaker Should You Use for a 5500-watt Water Heater?

A 5500-watt, 240-volt water heater requires 22.9 amperes to work. Multiplying it by 1.25, you will get a final ampere rating of 28.645. Hence, a 30-amp circuit breaker should be sufficient for this setup.

What type of breaker is needed for a water heater?

Because your water heater runs on 240 volts, it also requires a double-pole circuit breaker. This CB type has two live wires. If a problem occurs in one of the wires, it also trips the other to cut off electricity to the water heater.

How Does Electricity Heat the Water?

Your residential electrical system’s voltage pushes electrons as amperes through a conducting wire. All wires offer resistance, reducing electrical flow. It also creates heat.

What Size of Wiring Do I Need for My Water Heater?

In general, the smaller the diameter of the electric wire, the faster it tends to heat. That is why it is best to get a wire with a large gauge.

What is a Circuit Breaker and Why Do You Need It?

Remember what we said about the voltage pushing the electrons through the wire, producing heat? If there is excessive heat on the wires, it can melt the wire covering and start a fire. There must be a mechanism that will stop the flow of electricity from the source to the water heater.

What is the Correct Circuit Breaker Size?

Manufacturers rate circuit breakers according to the maximum electric current (in amperes) they can accommodate without tripping or breaking the circuit.

How many amps does a 240 volt water heater need?

In other words, the size of circuit breaker you will need for a 4500-watt, 240-volt water heater is 25 or 30 amperes.

How many amps does a water heater need?

This 240-volt circuit serving the water heater should also have a 30-amp double-pole circuit breaker.

How many amps does a 120 volt water heater draw?

For instance, an electric water heater with 1,500 watts running on 120 volts will have a maximum current draw of 12.5 amperes (1,500 divided by 120 = 12.5).

What is a circuit breaker?

Circuit breakers protect your home’s electrical circuit against short circuits, overloading, and overcurrent by interrupting electric current flow when it detects a fault. In essence, it also protects your water heater. That is why you need to choose the right size of a circuit breaker to use with your water heater.

What is the gauge of a wire?

The wire gauge is inversely proportional to the conductor’s diameter. As such, the greater the wire gauge number, the smaller is the conductor’s diameter. For example, a 10-Gauge wire has a cross-sectional area of 5.26 square millimeters and a diameter of 0.1019 inches.

Is it better to get a 20 amp or 15.6 amp breaker?

It would be more appropriate to get a 20-ampere circuit breaker than a 15.6-ampere unit, referring to our computation above. Getting a breaker with the next higher amperage rating minimizes overloading your system and saves you from electrical accidents.

What Size Disconnect Do I Need For A Water Heater?

The average water heater runs on a 240V circuit. It requires a 30A double-pole breaker and 10-2NM cable.

How to find amperage of a 4500 watt?

Once you know the wattage and voltage ratings, you can find the amperage. It is a simple matter of dividing the wattage by the voltage. In other words, 4500/240. The answer is 18.75A.

How many heating elements does a 120V water heater have?

SFGATE says that water heaters that run on 120V have one heating element. They are not very appealing because their recovery time is far too long.

What happens if a water heater malfunctions?

If a water heater malfunctions, the amount of electricity it uses is more than capable of causing lasting harm or killing the occupants of your home.

Can you see the water heater switch while standing?

It isn’t enough for you to ensure that you can see the switch from the water heater. You should be able to see the water heater while standing at the switch. Otherwise, you may incur a penalty from a, particularly strict inspector.

Do you have to pair a water heater with a disconnect?

Don’t forget the law. If your local code expects you to pair a water heater with a disconnect, you must comply.

Can you cut the power of a water heater by pulling the cord out?

Water heaters with cords are somewhat rare these days. But they exist. The plug is very important in this scenario because it acts as a disconnect. You can cut the power by simply pulling the plug out. That being said, just like the panel, the plug should be within the water heater’s line of sight.

What size wire for a 4500-watt water heater?

If this is the case, then a 30 amp breaker will cause an unsafe condition. The way it’s geared up now is a 12/2, 20 amp twin breaker. The Rheem tank I have takes 3500 watts.

Can the wiring to a water heater be extended via a junction box?

The existing wiring to a proposed new water heater will come up about 2-3 feet short. The way it’s currently run, it offers zero slacking to work .

Does 30A work well with 12 wires?

The inspector found a 12-gauge wire attached to a 30-amp breaker. A common issue with this configuration is that the wire may overheat and fire before the breaker trips.

Can 10/2 wire be used for a water heater?

Your breaker size would be 25 when using wire 10/2 when upgrading from a 60 gallon to a 40 gallon.

1.What Size Breaker Do I Need for a 4500 Watt Water …

Url:https://www.galvinpower.org/what-size-breaker-for-4500w-water-heater/

27 hours ago  · Calculating the breaker size for a 4500-watt water heater. The right size of a circuit breaker is calculated by dividing the total wattage of the load by the supply voltage. In this …

2.What Size Breaker for a Hot Water Heater: A Breaker Size …

Url:https://www.galvinpower.org/what-size-breaker-for-a-hot-water-heater/

1 hours ago  · With our answer, a 40-gallon water heater needs at least a 25-amp breaker, the closest to the amperage value. However, I highly recommend using 30-amps for a safer …

3.4500 Watt Hot Water Heater Breaker Size - Muhammad …

Url:https://muhammadardhi.com/4500-watt-hot-water-heater-breaker-size/

32 hours ago With 240 volts, a 40-gallon heater operates on an average of 4500 Watts. Assuming I = P/V, 4500W/240V equals 18.75 amps. Taking into account the continuous load (125% x 18.75A), …

4.What Size Breaker Do I Need for a Water Heater?

Url:https://www.usawaterquality.org/what-size-breaker-do-i-need-for-a-water-heater/

9 hours ago  · In other words, the size of circuit breaker you will need for a 4500-watt, 240-volt water heater is 25 or 30 amperes. You may think that a 20-amp circuit breaker is enough for a …

5.What Size Breaker for a Hot Water Heater?

Url:https://www.usawaterquality.org/what-size-breaker-for-a-hot-water-heater/

26 hours ago  · 18.75 volts at 18.75 amps In addition to the size of wire mentioned above, what size wire do I require for a hot water heater? The wire gauge for a 20-amp hot water heater …

6.Does A Water Heater Need A Disconnect? Amp, Height, …

Url:https://portablepowerguides.com/does-a-water-heater-need-a-disconnect/

25 hours ago  · For an electric water heater, you’ll need a breaker that’s at least 30 amps, while for a gas water heater, it should be at least 20 amps. But it’s always better to be cautious and get a …

7.What Size Wire for 4500-watt Water Heater and What …

Url:https://muhammadardhi.com/what-size-wire-for-4500-watt-water-heater/

29 hours ago  · This 240-volt circuit serving the water heater should also have a 30-amp double-pole circuit breaker. If your water heater connects to a 120-volt system, a 20-ampere single …

A B C D E F G H I J K L M N O P Q R S T U V W X Y Z 1 2 3 4 5 6 7 8 9