What size breaker do I need for a 100 amp sub panel? You can feed a 100 amp panel with a 60 amp breaker, theres no problem there. Running smaller wire will save you quite a bit. Yes you will need 4 wires, and you can use 3#6 thhn and a ground which could be #8.
Full Answer
Can I use a 100 amp breaker for a sub panel?
If it is used for lights, it will probably be okay. Nope. The breaker protects the wire leading to that subpanel. The “100 amp” rating of the subpanel is the max rating that you can feed it at.
Can I plug a 60 amp breaker into a 100 amp circuit?
Stream SiriusXM for 3 months for free. See Offer Details. You can put a 60 amp breaker in a sub panel to supply a branch circuit if that sub panel is truly rated for 100 amps and is being supplied by a 100 amp breaker in the main panel including correct size conductors supplying the sub panel.
Does a 100A box have a main breaker?
The sub panel is a 100A box doesn’t have a main breaker. If I have 50A in the main, how high can I go in both panels to get the power I need without creating issues?
How many amps does a 240 volt main breaker use?
The main breaker needs to be two-pole, in order to interrupt both line conductors at the same time. But the service is 100 amps total at 240 V. Since most of the loads in the house are 120 V, not 240 V, you can think of this as being 200 amps at 120 V if you want, but it’s still called a 100 A service
How long does it take for a 60 amp breaker to trip?
How many amps per circuit?
Can you go off breaker size?
Can you overlap loads?
Can a 60A breaker be used in a 30A subpanel?
See 2 more
About this website
Can I feed a 100 amp subpanel from a 60 amp breaker?
You can feed a 100 Amp panel with a 60 Amp breaker. Keep in mind that the sub panel needs to be rated above the breaker size.
Can I feed a 100 amp subpanel with a 50 amp breaker?
Using a larger sub panel will not be a problem but the breaker must stay a 50 AMP in the main panel. You can utilize the 50 Amp breaker in the hot tub panel as a connection point for the new wire run or just use that junction as a splice point.
Can you run a sub panel off a 60 amp breaker?
A 60-amp subpanel can power lighting and general-use outlets in another section of your home. But if you only have a 60-amp service and want to add a 60-amp subpanel, you'll have to upgrade your main panel first to allow such a distribution addition. However, many modern-day homes can already use close to 200 amps.
What size breaker do you need for a 100 amp sub panel?
Typical 100-amp panels have 20 circuits, meaning they can handle 20 full-sized breakers. 20/24 panels can hold 16 full-sized and 4 twin breakers (24 circuits in total). The number of breakers can max out to 30-42, too, depending on the design of your 100-amp pane.
How many 100 amp breakers can you put in a 200 amp panel?
Nothing inherently wrong with 2 100A breakers in one box plus lots of other breakers - i.e., oversubscribing the 200A total is perfectly fine if real-world usage will stay under 200A.
How many amps can you put on a 100 amp panel?
For example, a 100-amp service panel could have circuit breakers that add up to more than 200 amps.
How far can a subpanel be from the main panel?
The right feet would be between 4.5 to 5 feet. The cable from your main panel to the subpanel depends on the amperage rating. For instance, for a 30A panel, use a 10 AWG, three-wire conductor.
Can I run a 100 amp sub panel off 200 amp main?
Of course you can, you can add the 100 amp breaker to your 200 amp as long as it isn't overloaded, to start adding the subpanel you must first calculate how many yards it will be from the main panel to the subpanel, there is a formula that calculates how much friction will be on the wire at the connecting distance, ...
How big of a sub panel can I install off a 200 amp service?
Even though there is no limit on the number of subpanels you can add to a circuit, it shouldn't exceed 160 amps when using a 200 amp main panel.
Can I run a sub panel off 100 amp main?
Let me try and answer some of your questions. First the panels you are looking at that are rated 100A simply means you can use them for any application up to 100A.
Does a subpanel need a ground rod?
Yes, any sub panel outside of the main building requires it's own ground rod and a ground wire back to the main building.
What size wire do I need for 100 amp sub panel 100 feet away?
If you check the wire size chart (you have the link in the introduction), the #0 AWG wire (also known as 1/0 AWG wire) has 150 ampacity. That means that #0 AWG wire is the perfect size wire for 100 amp service 100 feet away.
What wire do I use for a 100 amp sub panel?
#4 copper wiresThe cable must have a wire gauge sufficient to the amperage of the subpanel—a 100-amp subpanel requires #4 copper wires or, more commonly, #2 aluminum wires, for example. (Aluminum is often used for feeder cables because the cost is typically much lower than that of copper wires.)
What can I run off a 50 amp breaker?
A 50-amp breaker can run appliances like ovens, hairdryers, air conditioners, and multiple lights simultaneously while (possibly) still sparing power. The reason for this breaker's capacity is because it can hold up to 12,000 watts running on a 240-volt circuit (50-amps x 240-volts).
How many amps can a 50 amp breaker handle?
The National Electrical Code or NEC puts a circuit breaker's maximum continuous current capacity at 80% of its rating. This regulation means that a 50-amp circuit should only carry a maximum continuous load of up to 40 amps.
Can I run a 100 amp sub panel off 200 amp main?
Of course you can, you can add the 100 amp breaker to your 200 amp as long as it isn't overloaded, to start adding the subpanel you must first calculate how many yards it will be from the main panel to the subpanel, there is a formula that calculates how much friction will be on the wire at the connecting distance, ...
Can you feed a 100 amp sub panel with a 60 amp breaker? - Quora
Answer (1 of 6): Yes you can… Are you replacing the main breaker or just putting it in? I mean, you can install any breaker you wish as a main breaker as long as it is not larger than the rating of the panel board and your wires to it are large enough for it. There are more things to consider as...
What size wire should I use for a 60amp subpanel?
The National Electrical Code Book / Article 110.14 (c)(1) identifies temperature limitations for circuits and feeders of 100 amp or less. If the circuit is 100 amp or less you have to size the conductors based on the 60-degree celsius column unless the breaker and the equipment terminations are rated for 75 or 90 degrees.
electrical - 60A two pole breaker supplying a sub panel (220v) - how ...
I'm trying to wrap my mind around how many amps 220V wire (two hot poles) can supply, when it's effectively supplying a multi wire branch circuit (sub panel)... My question is this: if the sub pan...
Can I run a 60amp sub panel from my main panel to my garage…
if I understand your question correctly. The main panel is in the basement and I've already run 6/3 to the garage for the hot tub (it will be just outside the garage).
CEC - 60 amp sub panel with 100 amp breaker in it
Using the 100 amp main breaker as a disconnecting means for a sub-panel is okay, because the OCPD is 60 amps at the main panel. In this instance, it'll just be a disconnect for you to work in the panel and see the disconnecting means in the off/open position.
How long does it take for a 60 amp breaker to trip?
There is a fairly large safety factor built into wiring standards and the short peak period of both units do start at the same time will probably still be ok because breakers are inverse time rated, this means they can supply current above their rated value for a short time, most breakers do not immediately trip at their set value but 10 seconds or more after reaching this value based on their trip curves. The higher the current the faster they trip so your actual load could be 150 amps for a few seconds with out tripping the 60 amp breaker since it is only a few seconds the wiring doesn’t have time to heat up and damage the insulation this is the key. When everything is up to speed and cycling normally we like the load to be at 80% .
How many amps per circuit?
So you can provision 4.5 amps per circuit or whatever, as appropriate.
Can you go off breaker size?
You really cannot go off breaker sizes for ac units. The reason I say this is because this is one place code allows larger breakers than the wiring can support. How can code allow larger breakers than the wiring can support? It is because of the starting current, this can and many times is 5x the running value of the unit (with conventional ac systems) on a newer system with a variable frequency drive they don’t have as high starting currents and vary the speed to save $.
Can you overlap loads?
Obviously you can overlap loads which are mutually exclusive, like heat pump emergency heat and A/C.
Can a 60A breaker be used in a 30A subpanel?
Probably not. While the 60A breaker's primary job is to protect the wiring between the panel and the subpanel, you can have breakers totaling more than 60A in the subpanel. But with a 40A AC unit and a 30A AC unit, you will almost certainly have both running at once and that will almost certainly overload the circuit and pop the 60A breaker.
How many amps does a triplex need?
The triplex sizes fall under a different set of sizing rules. You need the correct size from the weatherhead to the meter and meter to panel to upgrade to 100 amps.
How many votes on 42 posts?
Received 44 Votes on 42 Posts. Usually that wire is owned by the power company, so it is not the property owner's concern. You tell them how much power you actually use (not necessarily the same as the service or panel size), and they select and install an appropriate wire. Upvote.
Is number 2 overhead OK for 100A service drop?
Number 2 overhead is OK for a 100A service drop.
Is #2 wire OK for 100 amps?
#2 is OK, but that is their wire. You need to look at the wire size from the attachment point to the line side of the meter, and the wire on the load side of the meter to the main panel. If all that is #2 AL or #4 copper, then it would be OK for 100 amps. Power companies today will normally run 200 amp wire regardless of the service size to a house unless it over 200 amp. Keeps everything standard.
Can you back feed a 60 amp breaker?
You could back feed the 60 amp breaker until you can upgrade the service. You would need as breaker hold down installed on the 60.
Can you connect a feeder to a meter?
You wouldn't be connecting to the feeder to the meter. The meter would not be involved with installing the subpanel. When your ready for a new meter at the house it would be better to install a new service including meter socket and main disconnect. Once that was energized you could just switch the subpanel to it.
How long does it take for a 60 amp breaker to trip?from diy.stackexchange.com
There is a fairly large safety factor built into wiring standards and the short peak period of both units do start at the same time will probably still be ok because breakers are inverse time rated, this means they can supply current above their rated value for a short time, most breakers do not immediately trip at their set value but 10 seconds or more after reaching this value based on their trip curves. The higher the current the faster they trip so your actual load could be 150 amps for a few seconds with out tripping the 60 amp breaker since it is only a few seconds the wiring doesn’t have time to heat up and damage the insulation this is the key. When everything is up to speed and cycling normally we like the load to be at 80% .
How many amps per circuit?from diy.stackexchange.com
So you can provision 4.5 amps per circuit or whatever, as appropriate.
Can you go off breaker size?from diy.stackexchange.com
You really cannot go off breaker sizes for ac units. The reason I say this is because this is one place code allows larger breakers than the wiring can support. How can code allow larger breakers than the wiring can support? It is because of the starting current, this can and many times is 5x the running value of the unit (with conventional ac systems) on a newer system with a variable frequency drive they don’t have as high starting currents and vary the speed to save $.
Can you overlap loads?from diy.stackexchange.com
Obviously you can overlap loads which are mutually exclusive, like heat pump emergency heat and A/C.
Can a 60A breaker be used in a 30A subpanel?from diy.stackexchange.com
Probably not. While the 60A breaker's primary job is to protect the wiring between the panel and the subpanel, you can have breakers totaling more than 60A in the subpanel. But with a 40A AC unit and a 30A AC unit, you will almost certainly have both running at once and that will almost certainly overload the circuit and pop the 60A breaker.
What breaker is used for 100 amp subpanel?
Generally, when installing a 100-amp sub-panel, it would be connected by a 100-amp breaker.
How many amps does a breaker have?
Each breaker on the main panel or a sub-panel connects a circuit of power somewhere in your home. These are generally 120-volt circuits (15-20 amps) that run most household items. In bedrooms and living rooms, there are usually 15-amp circuits that connect lighting and outlets in a specific area. 20-amp circuits typically supply areas like kitchens or garages where there are larger appliances.
What is a sub panel breaker?
On the main panel, there will be circuit breakers for each circuit. If there is a sub-panel, then there will be a large breaker that connects to it. This breaker would supply the feeder circuit that powers the sub-panel and would be a double-pole breaker with double-size levers.
What is a sub panel in a circuit?
On the main panel, there would be a breaker specifically linking the sub-panel to the main supply. The sub-panel would, therefore, control a branch circuit from the main panel. This branch circuit would then get divided into multiple smaller circuits fed from the sub-panel.
What is a sub panel?
The sub-panel connects to the main panel via a circuit breaker in the main panel. This is known as a feeder breaker and is a 240-volt circuit breaker. Because it is a double-pole breaker, it will take up two adjacent spaces on the main panel, so you need to have or create capacity for that.
Why do you need a sub panel?
Homeowners install sub-panels either to extend the available circuit space of their main panel or to connect a distant part of their property to the main panel. Whatever the reason, it’s essential that the installer correctly connects the sub-panel via a double-pole breaker. Safety should be the primary concern when working on anything with electricity within the home. It is recommended to always get a professional to do any work with electricity.
What is the purpose of a circuit breaker panel?
This circuit breaker panel protects your wiring, and the breaker design trips if there is an overload.
How long does it take for a 60 amp breaker to trip?
There is a fairly large safety factor built into wiring standards and the short peak period of both units do start at the same time will probably still be ok because breakers are inverse time rated, this means they can supply current above their rated value for a short time, most breakers do not immediately trip at their set value but 10 seconds or more after reaching this value based on their trip curves. The higher the current the faster they trip so your actual load could be 150 amps for a few seconds with out tripping the 60 amp breaker since it is only a few seconds the wiring doesn’t have time to heat up and damage the insulation this is the key. When everything is up to speed and cycling normally we like the load to be at 80% .
How many amps per circuit?
So you can provision 4.5 amps per circuit or whatever, as appropriate.
Can you go off breaker size?
You really cannot go off breaker sizes for ac units. The reason I say this is because this is one place code allows larger breakers than the wiring can support. How can code allow larger breakers than the wiring can support? It is because of the starting current, this can and many times is 5x the running value of the unit (with conventional ac systems) on a newer system with a variable frequency drive they don’t have as high starting currents and vary the speed to save $.
Can you overlap loads?
Obviously you can overlap loads which are mutually exclusive, like heat pump emergency heat and A/C.
Can a 60A breaker be used in a 30A subpanel?
Probably not. While the 60A breaker's primary job is to protect the wiring between the panel and the subpanel, you can have breakers totaling more than 60A in the subpanel. But with a 40A AC unit and a 30A AC unit, you will almost certainly have both running at once and that will almost certainly overload the circuit and pop the 60A breaker.