how often do you support mc cable

by Lucio Reilly II Published 2 years ago Updated 2 years ago
image

6 feet

Full Answer

How often does MC Cable need to be secured?

It must be secured at least every 6 ft. Additionally, MC cable containing four or fewer conductors of size 10 AWG or less is required to be secured within 12 in. from every box, cabinet, or fitting. Both requirements are illustrated in Exhibit 330.2.

How far should MC Cable be from outlet?

However, the MC cable must be secured (fastened in place) within 12 in. of the outlet box. Staples, cable ties, or clamps would be necessary to secure a cable. (B) Securing. Unless otherwise provided, cables shall be secured at intervals not exceeding 1.8 m (6 ft).

When is MC Cable unsupported?

Type MC cable shall be permitted to be unsupported where the cable: (2) Is not more than 1.8 m (6 ft) in length from the last point of cable support to the point of connection to luminaires or other electrical equipment and the cable and point of connection are within an accessible ceiling.

What is the difference between securing and supporting MC Cable?

There is a difference between securing and supporting. Type MC cable that runs horizontally through or on framing members or racks (spaced less than 6 ft apart) without additional securing is considered supported. Staples or cable ties are not required as the cable passes through or on these members.

What is 330.30 D?

How far apart do you secure a MC cable?

Is a MC cable a support cable?

About this website

image

Does MC cable need to be protected?

Type MC cable installed through or parallel to framing members or furring strips must be protected against physical damage from penetration of screws or nails by maintaining a 1¼ in. separation, or by installing a suitable metal plate in accordance with Sec. 300.4(A), (C), and (D) [330.17].

Do you have to derate MC cable?

Q: Is it necessary to derate types NM-B, AC or MC cables where these cables are bundled to enter a branch-circuit panelboard? A: Generally, where cables are bundled for more than two feet without maintaining spacing between them, derating of the contained conductors is required.

Where is MC cable required?

Type MC cable installed on the bottom of floor or ceiling joists must be secured at every joist and not be subject to physical damage [Sec. 330.15].

Can you support MC with zip ties?

Yes, cable ties are permitted. Section 330.30(A) provides the general requirements and permits cable ties.

How long can you run MC cable?

6 ft.of every outlet box, junction box, cabinet, or fitting and at intervals not exceeding 6 ft. Type MC cable must be supported at intervals not exceeding 6 ft. Cables installed horizontally through wooden or metal framing members are considered secured and supported where such support doesn't exceed 6 ft intervals.

Where is MC cable not permitted?

MC cables are not permitted to be installed where subject to physical damage.

How many MC cables can you run through a hole?

According to the National Electrical Code, you can have 4 12/2 nonmetallic sheathed cables through a single bored hole that is fire- or draft-stopped using thermal insulation, caulk, or sealing foam, or where proper spacing is not maintained for more that 24 in.

How many MC wires can be bundled together?

20(a) Each cable cannot have more than three current-carrying conductors. (b) The conductors are No. 12 AWG copper minimum. (c) Not more than 20 current-carrying conductors are bundled, stacked, or supported in bridle rings.

What is the NEC code for strapping MC cable?

Article 330.30According to NEC Article 330.30, MC cable must be supported and secured at intervals of 6 feet or less (unless routed through a framing member) and cables containing four or fewer conductors sized no larger than 10 AWG must be secured within 12 inches of every termination.

Can staples be used for MC cable?

2:313:16Are DeWalt Cable Stapler Staples Legal for MC Cable by 2020 NEC?YouTubeStart of suggested clipEnd of suggested clipSay the answer is yes these staples and this cable stapler can be used with mc cable. So if you saidMoreSay the answer is yes these staples and this cable stapler can be used with mc cable. So if you said yes you're right i'll put a link in my video description for the dewalt cable stapler i'll also put

Are anti shorts required for MC cable?

Anti-short bushings that may be supplied by MC Cable manufacturers are for optional use by the installer, however they are not required.

Can you strap MC cable to EMT?

you can tie wire FMC and MC to emt I would think if your going to stap it like that you have chosen a path for your home runs and you have built it in a way that you have planned for the extra weight. If you have a pipe run that just runs from point a to point b with min strapping you can not strap to it.

Are anti shorts required for MC cable?

Anti-short bushings that may be supplied by MC Cable manufacturers are for optional use by the installer, however they are not required.

Can you run MC cable through conduit?

Oh, separately, do not put MC inside of PVC or EMT conduit. This doesn't make it suitable for wet locations. You can't take a non-waterproof wire or cable and run it in a conduit to make it waterproof; that's not allowed.

Can you run MC cable into a plastic box?

MC Cable Is for Metal Boxes Only! Plastic or fiberglass electrical boxes aren't designed to be used with MC cable. Even if you're able to rig up a connection to a plastic box, you will fail the electrical inspection.

Can you run MC cable exposed in garage?

Type MC Cable without an outside nonmetallic jacket can be installed in an “other space used for environmental air” in accordance with Section 300.22(C). These cables can be installed either indoors or outdoors and in exposed and concealed locations.

Support of MC cable above suspended cieling | Mike Holt's Forum

I was failed on an above ceiling inspection because I supported mc cable on the ceiling grid wire 300.11.2 Exception allows this in a non fire rated ceiling as long as it is installed per the manufacture's instructions.

What is 330.30 D?

Section 330.30 (D) (1) permits Type MC cable to be fished. Section 330.30 (D) (2) permits listed MC cable fittings to support the last 6 ft of MC cable supplying a luminaire in an accessible ceiling. This use is in accord with 320.30 (D) (3) for Type AC cable.

How far apart do you secure a MC cable?

However, the MC cable must be secured (fastened in place) within 12 in. of the outlet box. Staples, cable ties, or clamps would be necessary to secure a cable. (B) Securing. Unless otherwise provided, cables shall be secured at intervals not exceeding 1.8 m (6 ft).

Is a MC cable a support cable?

There is a difference between securing and supporting. Type MC cable that runs horizontally through or on framing members or racks (spaced less than 6 ft apart) without additional securing is considered supported. Staples or cable ties are not required as the cable passes through or on these members. However, the MC cable must be secured (fastened in place) within 12 in. of the outlet box. Staples, cable ties, or clamps would be necessary to secure a cable.

What is the most common size of FMC cable?

It also allows you to add wires in the future, something you can’t do with MC cable. FMC is identified by its diameter; the most common sizes are 1/2-in., 3/4-in. and 1-in. 4 / 12.

How to cut MC cable?

If you just have one or two cuts to make and don’t want to invest in a cutting tool, bend the MC cable sharply until the armor pops open, and then use that opening to start the cut with a side/diagonal cutter. You only need to cut through one section in the armor. This method will leave a jagged edge that will need to be trimmed after the armor is separated and the cut ends of the MC cable will be sharp, so be sure to wear gloves.

What Is Metal-Clad Cable?

Metal-clad cable comes in several varieties, but the type you’ll find most commonly is three insulated wires (two circuit conductors and a green equipment grounding conductor) protected by a flexible armor usually made from aluminum. MC cable is identified by the gauge of the wire, not the diameter of the armor. The most common sizes are 14 gauge, 12 gauge, and 10 gauge.

What is a greenfield cable?

Flexible metal conduit (FMC) is commonly called “Greenfield.”. The main difference between MC cable and FMC is that FMC doesn’t have the insulated wires pre-installed; you have to pull them through instead. This requires more work but gives you the option of pulling, and protecting, more than one circuit in the same conduit.

Can you use MC cable with plastic box?

Plastic or fiberglass electrical boxes aren’t designed to be used with MC cable. Even if you’re able to rig up a connection to a plastic box, you will fail the electrical inspection. Make sure the metal box has knockout holes located where you need them, and don’t rely on the spurs on the bracket to hold the box in place—add a couple of screws as well.

Can you attach a connector to a MC cable?

You can attach a connector to MC cable, then join it to the box, but it’s easier to mount the connector on the box before feeding the wires through. Connectors like those shown above are popular with electricians because the one screw secures both the connector to the box and the MC cable to the connector.

What section of the NEC prohibits the use of conductive pool shells?

Revisions in the 2017 NEC specifically prohibit the use of a conductive pool shell or perimeter surface bonding from being used as a grounding electrode. Section 250.52 (B) now prohibits the use the structures and structural reinforcing steel described in 680.26 (B) (1) and (B) (2).

What is considered a structure in a building?

For example, a 4-by-4 post, a concrete pad, an EV charger, a lamp post, a canopy and any equipment installed outdoors would be considered a structure because it is all “built or constructed.” Section 250.32 contains requirements for buildings or structures supplied by feeders or branch circuits. The general rule for buildings or structures supplied by feeders or branch circuits is that a grounding electrode system (GES) be established.

What is 240.80?

Section 240.80 provides requirements for the operation of circuit breakers and mandates that all circuit breakers be trip-free and capable of being closed and opened manually. The term “trip free” when applied to molded-case circuit breakers means that the contacts inside the device cannot be held closed when an abnormal condition exists. This means an accessory device that is applied to the handle of the circuit breaker to hold it in the “on” position cannot prevent the device from opening internally due to overload or short-circuit conditions.

How many chapters are there in the NEC?

The NEC has nine chapters; 1 through 4 apply generally. Therefore, they apply to all electrical installations. Chapters 5, 6 and 7 are special and have always supplemented or modified the requirements in chapters 1 through 4. This arrangement is revised in the 2017 NEC, and chapters 5, 6 and 7 may now supplement or modify ...

What is an example of a special article modifying another special article?

An example is seen in Article 760, Fire Alarm Systems. Section 760.3 explains that the only requirements of Article 300 that apply are those referenced within the article. An example of one special article modifying another special article is seen in Section 517.26. This requires the life-safety branch of the essential electrical system to meet the requirements of Article 700, except as amended by Article 517.

What is a structure in construction?

The new definition of structure is “that which is built or constructed other than equipment.” This is a significant improvement but will not solve this problem. Equipment typically needs some type of support or foundation. A 4-by-4 post or concrete pad does not constitute a structure; it is simply a means of support.

What is a 2S cable tie?

Type 2S or Type 21S cable ties are now recognized as capable of providing “securement and support” for cable assemblies and flexible conduit. The suffix “S” denotes the capability of providing “securement and support.” Where cable ties are marked as Type 1, Type 11, Type 2 or Type 21, without the “S” suffix, they may be used for other purposes, including, but not limited to, bundling, routing or grouping of cables and conductors. It is also important to note that, where cable ties are used in other spaces used for environmental air (for example, the space above a hung ceiling used for return air), they must be also listed as having low smoke and heat-release properties as required in Section 300.22 (C).

What is PVC jacketed MC?

PVC-jacketed MC has a coating over the length of it that makes the inside of the conductor impervious to moisture. It also allows for the conductor to be in direct contact with the earth for use in direct-burial applications.

How many times the diameter of a conductor?

Twelve times the overall diameter of one of the individual conductors or seven times the overall diameter of the multiconductor cable, whichever is greater.

How long is 330.30 D?

330.30 (D) (2) Is not more than 1.8 m (6 ft) in length from the last point of cable support to the point of connection to luminaires or other electrical equipment and the cable and point of connection are within an accessible ceiling.

What is 330.30 D?

330.30 (D) (3) Is Type MC of the interlocked armor type in lengths not exceeding 900 mm (3 ft) from the last point where it is securely fastened and is used to connect equipment where flexibility is necessary to minimize the transmission of vibration from equipment or to provide flexibility for equipment that requires movement after installation.

Is MC cable the same as AC?

MC cable typically has either an insulated or bare FULL SIZED equipment grounding conductor inside of it – or sometimes both depending on the purpose of the MC. AC has a small #16AWG equipment grounding conductor in it. The codes in the 2017 NEC have variations in them between MC and AC on things such as bushings as well as the bonding conductor requirements, that is all to say, they are not the same thing. Think Metallica and Megadeth or Audioslave and Soundgarden. Essentially the same…but different.

Can MC cable be used indoors?

330 of the NEC mentions that MC cable can be used indoor and outdoor but does not make mention of it being allowed or disallowed for use in damp environments. It does state that when used in wet locations there must be a corrosion-resistant jacket to protect the conductors. However if you look into the UL listing for MC cable it is designed to be a dry-environment cable assembly. Use your discretion on this, but it’s always better to err on the side of caution when interpreting code. For wet and dry environments there is an MC cable assembly that is listed and approved for both.

Do you need to use anti short bushings with MC cable?

As of 2017 there is no requirement in the National Electric Code for MC to use anti-short bushings in MC cable installations. There is, however, a code which calls for them with the use of AC cable (320.40). Most wire-manufacturers include bundles of these bushing with every roll of MC cable they sell, as an courtesy in the event you choose to use them. You do not need to with MC. I find this a little bizarre, since AC and MC are fundamentally the same thing. The same problems exist in both instances, so I still prefer to use them. The national electric code is a minimum standard, which means you can go above and beyond them…you just can’t fall short.

What is 330.30 D?

Section 330.30 (D) (1) permits Type MC cable to be fished. Section 330.30 (D) (2) permits listed MC cable fittings to support the last 6 ft of MC cable supplying a luminaire in an accessible ceiling. This use is in accord with 320.30 (D) (3) for Type AC cable.

How far apart do you secure a MC cable?

However, the MC cable must be secured (fastened in place) within 12 in. of the outlet box. Staples, cable ties, or clamps would be necessary to secure a cable. (B) Securing. Unless otherwise provided, cables shall be secured at intervals not exceeding 1.8 m (6 ft).

Is a MC cable a support cable?

There is a difference between securing and supporting. Type MC cable that runs horizontally through or on framing members or racks (spaced less than 6 ft apart) without additional securing is considered supported. Staples or cable ties are not required as the cable passes through or on these members. However, the MC cable must be secured (fastened in place) within 12 in. of the outlet box. Staples, cable ties, or clamps would be necessary to secure a cable.

image

1.How often do you support MC cable? | Archive More

Url:https://carsom.mtagc.org/how-often-do-you-support-mc-cable/

20 hours ago According to NEC Article 330.30, MC cable must be supported and secured at intervals of 6 feet or less (unless routed through a framing member) and cables containing four or fewer conductors sized no larger than 10 AWG must be secured within 12 inches of every termination.

2.Supporting MC Cable | Mike Holt's Forum

Url:https://forums.mikeholt.com/threads/supporting-mc-cable.104505/

15 hours ago  · Section 330.30(B) contains the general requirements for supporting and securing Type MC cable. It must be secured at least every 6 ft. Additionally, MC cable containing four …

3.Vertical MC Cable Support in the 2014 NEC - IAEI …

Url:https://iaeimagazine.org/2014/januaryfebruary-2014/vertical-mc-cable-support-in-the-2014-nec/

11 hours ago  · How often do you strap Romex? How often do you strap Romex? General Cable Support Runs of NM cable must be supported at least every 54 inches. They also must …

4.MC Cable Installations - IAEI Magazine

Url:https://iaeimagazine.org/electrical-fundamentals/mc-cable-installations/

23 hours ago For vertical installations, any listed MC cable is allowed to be secured at 10 foot intervals (rather than the 6 foot interval required in the 2011 NEC) as long as the cable contains ungrounded …

5.Type MC Cable Support, Ground Rods And More

Url:https://www.ecmag.com/section/codes-standards/type-mc-cable-support-ground-rods-and-more

2 hours ago  · MC cable has no restrictions on the number of bends. The bending requirement for interlocked armor Type MC cable is “seven times the external diameter of the metallic …

6.WHAT YOU CAN AND CAN’T DO WITH MC CABLE

Url:https://electricianu.com/video/wiring-with-mc-what-you-can-and-cant-do-with-mc-cable/

32 hours ago How often do you support MC cable? According to NEC Article 330.30, MC cable must be supported and secured at intervals of 6 feet or less (unless routed through a framing member) …