
What is the difference between ASTM D and ASTM E?
Mar 01, 2020 · What is ASTM e84 Class A? Class A Fire & Smoke Rated This test measures a material's reaction after being exposed to fire, in terms of flame spread and smoke density. RealWall™ and LiteBarrier™ containment systems have an ASTM E-84 Class A rating, meaning they have the lowest fire spread rate and minimal smoke production. Click to see full answer.
What is ASTM E 84?
ASTM E84 (often referred to as just “E84”) is the standard test method for assessing the surface burning characteristics of building products. The purpose of this test is to observe the flame spread along a sample in order to determine the relative burning behavior of its material. Through the E84 test, both Flame Spread Index (FSI) and Smoke
How to get ASTM?
ASTM E84 Scope: This 10-min fire-test-response standard for the comparative surface burning behavior of building materials is applicable to exposed surfaces such as walls and ceilings. The test is conducted with the specimen in the ceiling position with the surface to be evaluated exposed face down to the ignition source.
What is Class A fire resistance?
Aug 30, 2011 · FSI values must be within 0 to 25 to be classified as Class A, 26 to 75 for Class B and 76 to 200 for Class C. All must also score 450 or lower in SDI. Many building codes use the ASTM E84 standard as a benchmark for construction materials, though it is important to always check local and individual building regulations before beginning any project or installation.

What is a Class A fire rating?
Flame spread classifications are developed using the American Society for Testing and Materials (ASTM) “tunnel test.” Class A fire ratings indicate flame-spread of 0-25 and smoke developed between 0-450 and is the highest of the ratings. The Class A or Class I rating indicates superior fire protection.
What is class A fire retardant?
Class A fire retardants have a flame spread rating of between zero and 25. These materials are effective against severe fire exposure. Class B fire retardants have a flame spread rating of between 26 and 75. These materials are effective against moderate fire exposure.
Is Class A non combustible?
Most non-combustible materials have a Class A flame spread rating allowing them to be used for walls and ceilings in a building. Fire resistant or fire resistance-rated refers to the fire ratings of the building's floors, wall, and ceilings.
Is Class A fire rating better than Class B?
Differences in fire performance between different materials can be evaluated by comparing flame spread ratings (Class A is the greatest resistance, followed by B and C) and heat release rate. Noncombustible materials are either defined as such in the building code, or have met the requirements of a standard test.Aug 27, 2019
What is fire rating of ASTM E84?
Both the RealWall™ and LiteBarrier™ containment systems have an ASTM E84 Class A rating, which means they have the lowest fire spread rate and minimal smoke production. It's important to note that not all containment systems on the market have been tested; in some cases, only certain components have been tested.
What does 1 hour fire rating mean?
A “one-hour” fire rating is given to an assembly consisting of various building materials that can resist the exposure of a standardized fire exposure for one hour.Aug 27, 2019
What is considered combustible construction?
Combustible refers to any material that will catch on fire and burn. As it relates to building materials, almost all types of lumber are considered combustible. This is important to understand as it can affect how it can be used based on the type of construction. Noncombustible is the opposite.May 12, 2020
What is the most fire resistant wood?
Most well known hardwoods such as mahogany, oak, maple and walnut are the ones with the highest fire resistance. Hardwoods are naturally more heat resistant due to their thickness and density. This ensures that they take some time to burn when subjected to heat or fire.
How long is Class A fire rating?
Class A - Flame-spread 0-25, smoke developed 0-450. Class B - Flame-spread 26-75, smoke developed 0-450. Class C - Flame-spread 76-200, smoke developed 0-450.
What fire rating is 20min?
A 20-minute fire-rated door is one that isolates a room during 20 minutes whilst exposed to fire. This kind of door is known as fire-rated EI2-20, and it is useful for places where you want extra protection even though a fire-rating is not demanded. Flame-proof doors usually also have some fire-rating.Feb 2, 2021
What is the highest fire rating?
350°F is the highest the internal temperature of the safe will become when exposed to a fire for 1 hr. UL rated fire safes work when the safe's exposure to heat is for less time than the stated time.Apr 15, 2021
What is the best flame spread rating?
A numerical reference that measures how fast and far a flame spreads during a 10-minute test. Flame Spread Index of 25 or less; the best possible rating, awarded to fire-retardant building products, like concrete.Aug 20, 2020
When is the E84 test required?
The 2006 International Building Code (IBC) specifies that 'interior wall and ceiling finishes shall be classified in accordance with ASTM E84.' Add...
How is the E-84 test run?
An E84 test is conducted by placing a 24' wide x 24’ long sample into a Steiner Tunnel (see description of Steiner Tunnel below), wherein the test...
What is a Steiner Tunnel?
Developed by Albert Steiner in the 1940s, the Steiner Tunnel is a steel box lined on its sides and floor with fire brick and featuring a removable...
Who does the E-84 fire and smoke testing?
Intertek currently operates four testing laboratories within North America certified to perform ASTM E84 Testing. In addition, our Coquitlam, Briti...
Is E-84 certification required?
No, certification is not required. However, because certification is a quality control process that helps to ensure that the product being tested i...
What if a product fails E-84? Passes?
ASTM E-84 is a comparative test, and as such, there is no real 'pass' or 'fail'. The test generates numbers expressed as Flame Spread Index (FSI) a...
What are the differences in the US and Canadian versions of the test?
The major difference that distinguishes the US from the Canadian version of the Steiner Tunnel Test is the way in which the sample is mounted in th...
Are all containment systems rated for E-84?
No, some products are not tested at all and others have only certain components of the products tested. When looking at E-84 ratings, make sure the...
Is E-84 the same as fire rated?
No, E-84 certifies the system does not exceed the FSI and SDI values after 30 minutes of fire. A fire rated system can withstand one hour of fire r...
What if the healthcare facility or local Fire Marshall is advocating for a fire-rated solution?
ASHE’s NFP 241 guidelines for temporary separation walls permit the use of non-fire rated walls when there is an approved automatic sprinkler syste...
When is the E84 test required?
The 2006 International Building Code (IBC) specifies that “interior wall and ceiling finishes shall be classified in accordance with ASTM E84.” Additionally, the National Fire Protection Agency (NFPA) 101® Life Safety Code® requires that “Interior wall or ceiling finish that is required elsewhere in this Code to be Class A, Class B, or Class C shall be classified based on test results from NFPA 255, ASTM E-84, or UL 723.”.
How is the E84 test run?
An E84 test is conducted by placing a 24” wide x 24’ long sample into a Steiner Tunnel (see description of Steiner Tunnel below), wherein the test is administered through the use of two burners which provide 89kW of energy.
What is a Steiner Tunnel?
Developed by Albert Steiner in the 1940s, the Steiner Tunnel is a steel box lined on its sides and floor with fire brick and featuring a removable lid. The tunnel contains a 12-in. high fire chamber with two burners at one end providing 89kW of energy. The Steiner Tunnel was adopted as an ASTM Standard in 1950 and given the designation of E84.
Who does the E84 fire and smoke testing?
Intertek currently operates four testing laboratories within North America certified to perform ASTM E84 Testing. In addition, our Coquitlam, British Columbia lab specializes in conducting CAN/ULC-S102 testing for the Canadian market.
Is E84 certification required?
No, certification is not required. However, because certification is a quality control process that helps to ensure that the product being tested is the product being manufactured, certification can be used to differentiate a product from similar market products.
What if a product fails? Passes?
ASTM E84 is a comparative test, and as such, there is no real “pass” or “fail”. The test generates numbers expressed as Flame Spread Index (FSI) and Smoke Developed Index (SDI), and while there are no pass-fail criteria in the standard, certain codes and regulations define required FSI value and/or SDI value for applications and installations.
What are the differences in the US and Canadian versions of the test?
The major difference that distinguishes the US from the Canadian version of the Steiner Tunnel Test is the way in which the sample is mounted in the testing chamber.
What are the different testing options for ASTM E84?
When testing a material for ASTM E84 you are presented with three different testing options, Unadhered, Adhered to GRC and Adhered to Gypsum. These options correlate to the end installation of the material. Depending on if it is for wallcovering, headboard, wrapped panels or something else there are different testing options that apply.
What is the Steiner tunnel?
Name: Steiner Tunnel or Steiner Tunnel Test#N#Purpose: Widely used method to determine the surface burning behavior (fire propagation and smoke development) of building materials of exposed surfaces such as walls and ceilings. #N#History: Developed in 1944 by Al Steiner of Underwriters Laboratories. Incorporated as a reference in North American standards for materials testing such as ASTM E84, NFPA 255, UL 723 and ULC S102.#N#Apparatus Description: The tunnel’s roof is a noncombustible horizontal box or tunnel, in a section 7.3 meters (24 ft) long and 0.56 meters (1.8 ft) wide. The tunnel is as wide and long as the test specimen, and 0.305 meters (1.00 ft) high. The apparatus is equipped with two gas burners providing a flame intensity of 89 kilowatts, and air and combustion products are moved through the tunnel by a ventilation system at a controlled velocity of 73 meters (240 ft) per minute.
What is the difference between Class A and Class B?
Class A rated materials produce minimal to no flames or smoke, while Class C produces the most. Class B materials generate a fair amount of both. FSI values must be within 0 to 25 to be classified as Class A, 26 to 75 for Class B and 76 to 200 for Class C. All must also score 450 or lower in SDI.
Is it safe to use a product that lacks safety?
No matter how useful or beneficial a product is, if it lacks safety, it shouldn’t be used. Some products can be inherently unsafe, no matter how they are utilized. Fortunately, these rarely make it to stores. Others are completely safe, provided they are used in the right way. Millions of products have many beneficial uses when used properly, ...
What is a Class A fire rating?
Here are key things to know about E84 Class Ratings: Class A always denotes products that offer a higher degree of performance when subjected to a fire.
When is a fire rated temporary wall required?
When conducting an occupied renovation in a hospital, a one-hour fire-rated temporary construction wall is often required by national or regional jurisdictions, particularly when a working sprinkler system is not in place.
